Danfoss SFA 15 safety relief valve, G 1/2 in x 3/4 in, set pressure 39 bar (566 psig), TUV certificate (code 148F3339)

Danfoss · HVAC & Refrigeration · Safety Relief Valves · Denmark · danfoss.com
Part Number
148F3339  ·  HS 8481.40
Danfoss SFA 15 safety relief valve, G 1/2 in x 3/4 in, set pressure 39 bar (566 psig), TUV certificate (code 148F3339)

Danfoss SFA 15 angle-way safety relief valve, code 148F3339, set pressure 39 bar (566 psig), supplied with a TUV pressure-setting certificate. The SFA 15 is a standard, direct-loaded, back-pressure-dependent safety relief valve specially designed to protect pressure vessels and other refrigeration components against excessive pressure. The spring housing is closed tightly to avoid refrigerant leakage. On a rise in pressure above the set pressure the valve initially starts to open slightly; it is fully open before the pressure is 10% above the set pressure and fully closed before the pressure is 10% below the set pressure. Inlet connection 15 mm (G 1/2 in) outside pipe thread to ISO 228/1, outlet 20 mm (3/4 in); inlet flow diameter (do) 13 mm (0.512 in), flow area (A0) 133 mm2 (0.206 in2), de-rated certified discharge coefficient (Kdr) 0.73, effective discharge area 97 mm2 (0.150 in2). Housing is special steel approved for low-temperature operation; spindle, cone and seat are stainless steel, and the cone gasket is a special chloroprene (neoprene) compound. Applicable for the refrigerants HCFC, HFC, R717 (ammonia) and R744 (CO2) within a temperature range of -50 to 100 C (-58 to 212 F); below -30 C full tightness is only guaranteed when the refrigerant pressure is equal to or lower than 0.5 x set pressure. The set pressure is adjusted and sealed at the Danfoss factory. PED 2014/68/EU conformity assessment category IV, fluid group I, 13 mm nominal bore. Specifications per Danfoss store code 148F3339.

Technical Specifications

TypeSFA 15 standard back-pressure-dependent safety relief valve
Code number148F3339
SeriesSFA (refrigeration safety relief valve)
Set pressure39 bar g (566 psig)
Pressure-setting range (family)10 to 40 bar g (145 to 580 psig)
DirectionAngle-way
Inlet connection15 mm (G 1/2 in) outside pipe thread, ISO 228/1
Outlet connection20 mm (3/4 in)
Inlet flow diameter (do)13 mm (0.512 in)
Flow area (A0)133 mm2 (0.206 in2)
De-rated certified discharge coefficient (Kdr)0.73
Effective discharge area (A0 x Kdr)97 mm2 (0.150 in2)
Opening characteristicfully open before +10% of set pressure; fully closed before -10% of set pressure
Housing materialspecial steel approved for low-temperature operation
Spindle, cone and seat materialstainless steel
Cone gasketspecial chloroprene (neoprene) compound
Media temperature range-50 to 100 C (-58 to 212 F)
Low-temperature notebelow -30 C full tightness only guaranteed when refrigerant pressure <= 0.5 x set pressure
Applicable mediaHCFC, HFC, R717 (ammonia), R744 (CO2)
Conformity assessmentPED 2014/68/EU, category IV, fluid group I
Classification (per OEM datasheet)DNV, CRN, BV, EAC (contact Danfoss for current list)
Pressure certificateTUV pressure-setting certificate supplied with each valve
ApprovalsCE, EAC
Net weight1.926 kg
Gross weight2.025 kg
EAN5702428193559

Properties

MaterialSpecial low-temperature steel housing; stainless steel spindle, cone and seat
Pressure rating39 bar (566 psig) set pressure
Temperature range-50 to 100 C
Standard sizeG 1/2 in inlet x 3/4 in outlet
Thread standardISO 228/1
MOQ1

Compatibility

Danfoss SFA 15 safety relief valve. Select strictly by required set pressure (this code is 39 bar / 566 psig); set pressures from 10 to 40 bar are available as separate factory-sealed order codes. The SFA is back-pressure dependent (a back pressure above atmospheric raises the opening pressure). It is recommended to install two valves in pairs together with a DSV 1 or DSV 2 double stop valve. Two certificate options exist at each set pressure: a Danfoss pressure certificate (148F32xx codes) or a TUV pressure-setting certificate (148F33xx codes) - this code carries the TUV certificate. Suitable for HCFC/HFC, R717 (ammonia) and R744 (CO2) refrigeration plant. For higher discharge capacity the SFA 15-50 variant uses the same body with a reduced Kdr.

Standards

Approvals

Attached Documents