Danfoss RT5A Pressure Switch 4 to 17 SPDT Manual Reset (017-504766)

Danfoss · Sensors & Instrumentation · Pressure Sensors · Denmark · danfoss.com
Part Number
017-504766  ·  HS 9032.20
Danfoss RT5A Pressure Switch 4 to 17 SPDT Manual Reset (017-504766)

Danfoss RT5A mechanical pressure switch with bellows sensing element, single-pole double-throw (SPDT) contact and manual maximum reset. Regulating range 4 to 17 bar; G 3/8 male pressure connection (ISO 228-1); enclosure IP54. Danfoss code number 017-504766.

Technical Specifications

BrandDanfoss
ModelRT5A pressure switch
Code number017-504766
Regulating range (Pe)4 to 17 bar
Maximum working pressure22 bar
Contact functionSPDT (single-pole double-throw)
ResetManual maximum
Differential1.3 bar (fixed)
Pressure sensing elementbellows
Pressure connectionG 3/8 male (ISO 228-1)
EnclosureIP54
Ambient temperature range-40 to +70 degC (-40 to +158 degF)
Cable entry2 x Pg 13.5
Contact ratingAC15=3 A at 400 V; AC1=10 A at 400 V; AC3=4 A at 400 V; DC13=12 W at 220 V; LR=28 A at 400 V
Maximum test pressure25 bar
EAN5702428517492
Net weight0.812 kg; gross weight: 0.922 kg
StandardsEN 60947-4, EN 60947-5
ApprovalsCE, EAC, CCC, CMIM, LVD, NKK, RMRS, PED
TypeRT5A
Product groupSwitches and thermostats
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalCCC
Burst pressure [bar]88 bar
CE markYes
China RoHS complianceYes
Differential [bar]1.3 bar
Differential [psi] [max]18.9 psi
Differential [psi] [min]17.4 psi
EEE category5 small equipment (any external dimension < 50 cm)
Electrical conn
Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2
Enclosure rating IPIP54
EU RoHS complianceYes
In scope of WEEEYes
Max. test pressure [bar] Pe25 bar
Max. test pressure [psig]363 psig
Max. Working Pressure [bar]22 bar
Max. Working Pressure [psig]320 psig
Other RoHS documentationSaudi Arabia RoHS
Pressure connection notesWeld nipple d6.5/D10mm
Pressure connection size3/8
Pressure connection standardISO 228-1
Pressure connection typeG
Pressure Male/FemaleMale
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR11
Regulation range [bar] Pe [max]17 bar
Regulation range [bar] Pe [min]4 bar
Regulation range [psig] Pe [max]246.6 psig
Regulation range [psig] Pe [min]58 psig
Reset functionManual Max
UL approved refrigerantsR11

Properties

MaterialBellows sensing element
Pressure rating22 bar
Temperature range-40 to +70 degC
IP ratingIP54
Thread standardISO 228-1
MOQ1

Compatibility

G 3/8 male (ISO 228-1) pressure connection. Confirm range and reset type against application.

Standards

Approvals

Attached Documents