Danfoss RT34 Thermostat -25 to 15 degC SPDT Auto Reset (017-511866)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
017-511866  ·  HS 9032.10
Danfoss RT34 Thermostat -25 to 15 degC SPDT Auto Reset (017-511866)

Danfoss RT34 mechanical temperature switch (thermostat) with room sensor and SPDT contact, auto reset. Sensor setting range -25 to 15 degC; differential 2 to 12 degC (adjustable); enclosure IP66. For industrial and marine refrigeration and HVAC applications. Danfoss code number 017-511866; EAN 5702428519182.

Technical Specifications

BrandDanfoss
ModelRT34 thermostat
Code number017-511866
Sensor temperature setting range-25 to 15 degC
Differential2 to 12 degC (adjustable)
Contact functionSPDT
ResetAuto
Sensor typeroom (ambient) sensor
Max. sensor temperature100 degC
EnclosureIP66
Ambient temperature range-50 to +70 degC
Cable entry2 x Pg 13.5
Contact ratingAC15=3 A, 400 V; AC1=10 A, 400 V; AC3=4 A, 400 V; DC13=12 W, 220 V; LR=28 A, 400 V
StandardsEN 60947-4, EN 60947-5
ApprovalsCCC, CE, EAC, LLC CDC EURO-TYSK, LVD, RMRS, RoHS, RoHS China, TYSK
EAN5702428519182
Part number017-511866
Net weight0.796 Kilogram
TypeRT34
Product groupSwitches and thermostats
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalCCC
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Diff. @ Max. range setting[°C] [max]12 °C
Diff. @ Max. range setting[°C] [min]2 °C
Diff. @ Min. range setting[°C] [max]10 °C
Diff. @ Min. range setting[°C] [min]2 °C
Differential typeAdjustable
Electrical conn
Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2
Enclosure rating IPIP66
EU RoHS complianceYes
Max. sensor temperature [°C]100 °C
Max. sensor temperature [°F]212 °F
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Temperature range [°C] [max]15 °C
Temperature range [°C] [min]-25 °C
Temperature range [°F] [max]59 °F
Temperature range [°F] [min]-11 °F

Properties

MaterialRoom sensor
Temperature range-50 to +70 degC (ambient); sensor -25 to 15 degC
IP ratingIP66
Primary standardEN 60947-5
MOQ1

Compatibility

RT34 room sensor thermostat. Confirm setting range, reset type and sensor/capillary length against application.

Standards

Attached Documents