cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Danfoss RT260AE ATEX Differential Pressure Switch 0.5 to 4 bar SPDT Auto Reset (017D003666)

Danfoss · Sensors & Instrumentation · Differential Pressure Sensors · Denmark · danfoss.com
Part Number
017D003666  ·  HS 9032.20
Danfoss RT260AE ATEX Differential Pressure Switch 0.5 to 4 bar SPDT Auto Reset (017D003666)

Danfoss RT260AE ATEX-rated mechanical differential pressure switch (Cat. 2, Zone 1) with bellows sensing element, SPDT gold contact and auto reset. Differential setting range 0.5 to 4 bar; G 3/8 male pressure connection (ISO 228-1); enclosure IP66. Danfoss code number 017D003666.

Technical Specifications

BrandDanfoss
ModelRT260AE differential pressure switch
Code number017D003666
Differential pressure range0.5 to 4 bar (0.05 to 0.4 MPa; 7 to 58 psi)
Contact functionSPDT, gold contacts
ResetAuto
Contact differential0.3 bar
Pressure sensing elementbellows
Pressure connectionG 3/8 male (ISO 228-1)
EnclosureIP66
Ambient temperature range-40 to +70 degC
Hazardous areaATEX Cat. 2, Zone 1
StandardsEN 60947-4, EN 60947-5
ApprovalsATEX Cat.2 Zone 1, CE, EAC, CCC, RMRS
EAN5702428131483
Net weight1.13 Kilogram
TypeRT260AE
Product groupSwitches and thermostats
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalATEX - Cat. 2 - Zone 1
CE markYes
China RoHS complianceYes
Contact differential [bar]0.3 bar
Contact ratingCi=0.5 nF
Diff.press.setting range [bar] [max]4 bar
Diff.press.setting range [bar] [min]0.5 bar
Diff.press.setting range [MPa] [max]0.4 MPa
Diff.press.setting range [MPa] [min]0.05 MPa
Diff.press.setting range [psi] [max]58 psi
Diff.press.setting range [psi] [min]7 psi
EEE category5 small equipment (any external dimension < 50 cm)
Electrical conn
Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2
Enclosure rating IPIP66
EU RoHS complianceOut of scope
EX Sales text-20C<ta<+65C
In scope of WEEEYes
Max. test pressure [bar] Pe25 bar
Max. test pressure [psig]362 psig
Max. Working Pressure [bar]22 bar
Max. Working Pressure [psig]319 psig
Operat. range LP side [bar] Pe [max]18 bar
Operat. range LP side [bar] Pe [min]-1 bar
Operat. range LP side [psig]Pe [max]261 psig
Operat. range LP side [psig]Pe [min]-15 psig
Pressure connection size3/8
Pressure connection standardISO 228-1
Pressure connection typeG
Pressure Male/FemaleMale
Pressure range [bar] Pe [max]18 bar
Pressure range [bar] Pe [min]-1 bar
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Relay release time [s]0 s
Reset functionAuto

Properties

MaterialBellows sensing element
Temperature range-40 to +70 degC
IP ratingIP66
Primary standardEN 60947-5
Thread standardISO 8434-1
MOQ1

Compatibility

ATEX Cat. 2 Zone 1 hazardous-area rated, gold contacts. G 3/8 male (ISO 228-1). Confirm zone classification against application.

Standards

Approvals

Attached Documents