cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss RT200 Pressure Switch 0.2 to 6 SPDT Manual Min Reset (017-523966)

Danfoss · Sensors & Instrumentation · Pressure Sensors · Denmark · danfoss.com
Part Number
017-523966  ·  HS 9032.20
Danfoss RT200 Pressure Switch 0.2 to 6 SPDT Manual Min Reset (017-523966)

Danfoss RT200 mechanical pressure switch with bellows sensing element, single-pole double-throw (SPDT) contact and manual min reset. Regulating range 0.2 to 6 bar; G 3/8 male pressure connection (ISO 228-1); enclosure IP54. Danfoss code number 017-523966.

Technical Specifications

BrandDanfoss Model: RT200 pressure switch Code number: 017-523966 Regulating range (Pe): 0.2 to 6 bar Maximum working pressure: 22 bar Contact function: SPDT (single-pole double-throw) Reset: Manual minimum Differential: 0.25 bar (fixed) Pressure sensing element: bellows Pressure connection: G 3/8 male (ISO 228-1) Enclosure: IP54 Ambient temperature range: -40 to +70 degC (-40 to +158 degF) Cable entry: 2 x Pg 13.5 Contact rating: AC15=3 A at 400 V; AC1=10 A at 400 V; AC3=4 A at 400 V; DC13=12 W at 220 V; LR=28 A at 400 V Maximum test pressure: 25 bar EAN: 5702423120932 Net weight: 0.896 kg; gross weight: 0.97 kg Standards: EN 60947-4
EN 60947-5 ApprovalsBV, CCC, CE, DNV, EAC, GL, KR, LR, LVD, NKK, RINA, RMRS
PED TypeRT200 Product group: Switches and thermostats Ambient temperature range [°C] [max]: 70 °C Ambient temperature range [°C] [min]: -50 °C Ambient temperature range [°F] [max]: 158 °F Ambient temperature range [°F] [min]: -58 °F Approval: BV CE mark: Yes China RoHS compliance: Yes Differential [bar]: 0.25 bar Differential [psi]: 3.6 psi EEE category: 5 small equipment (any external dimension < 50 cm) Electrical conn
Male/FemaleFemale Electrical connection: Screwed cable entry Electrical connection size: 2xPg 13.5 Electrical connection standard: DIN 40430 Electrical spec. standard: EN 60947-4/-5 EN 60947 electrical properties: Pollution degree: 3 EN 60947 wiring properties: Flex, ferrules: 0.2-1.5 mm2 Enclosure rating IP: IP54 EU RoHS compliance: Yes In scope of WEEE: Yes Max. test pressure [bar] Pe: 25 bar Max. test pressure [psig]: 363 psig Max. Working Pressure [bar]: 22 bar Max. Working Pressure [psig]: 320 psig Pressure connection size: 3/8 Pressure connection standard: ISO 228-1 Pressure connection type: G Pressure Male/Female: Male REACH Candidate List substances: Lead (CAS no. 7439-92-1) Refrigerants: R11 Regulation range [bar] Pe [max]: 6 bar Regulation range [bar] Pe [min]: 0.2 bar Regulation range [psig] Pe [max]: 87 psig Regulation range [psig] Pe [min]: 2.9 psig Reset function: Manual Min UL approved refrigerants: R11

Properties

MaterialBellows sensing element
Pressure rating22 bar
Temperature range-40 to +70 degC
IP ratingIP54
Primary standardEN 60947-5
Thread standardISO 228-1
MOQ1

Compatibility

G 3/8 male (ISO 228-1) pressure connection. Confirm range and reset type against application.

Standards

Approvals

Attached Documents