Danfoss RT17 mechanical temperature switch (thermostat) with room sensor and SPDT contact, auto reset. Sensor setting range -50 to -15 degC; differential 1.5 to 7 degC (adjustable); enclosure IP66. For industrial and marine refrigeration and HVAC applications. Danfoss code number 017-511766; EAN 5702428519199.
| Brand | Danfoss |
| Model | RT17 thermostat |
| Code number | 017-511766 |
| Sensor temperature setting range | -50 to -15 degC |
| Differential | 1.5 to 7 degC (adjustable) |
| Contact function | SPDT |
| Reset | Auto |
| Sensor type | room (ambient) sensor |
| Max. sensor temperature | 100 degC |
| Enclosure | IP66 |
| Ambient temperature range | -50 to +70 degC |
| Cable entry | 2 x Pg 13.5 |
| Contact rating | AC15=3 A, 400 V; AC1=10 A, 400 V; AC3=4 A, 400 V; DC13=12 W, 220 V; LR=28 A, 400 V |
| Standards | EN 60947-4, EN 60947-5 |
| Approvals | CCC, CE, EAC, LLC CDC EURO-TYSK, LVD, RMRS, RoHS, RoHS China, TYSK |
| EAN | 5702428519199 |
| Part number | 017-511766 |
| Net weight | 0.796 Kilogram |
| Type | RT17 |
| Product group | Switches and thermostats |
| Ambient temperature range [°C] [max] | 70 °C |
| Ambient temperature range [°C] [min] | -50 °C |
| Ambient temperature range [°F] [max] | 158 °F |
| Ambient temperature range [°F] [min] | -58 °F |
| Approval | CCC |
| CE mark | Yes |
| Charge type | State Vapour |
| China RoHS compliance | Yes |
| Diff. @ Max. range setting[°C] [max] | 5 °C |
| Diff. @ Max. range setting[°C] [min] | 1.5 °C |
| Diff. @ Min. range setting[°C] [max] | 7 °C |
| Diff. @ Min. range setting[°C] [min] | 2.2 °C |
| Differential type | Adjustable |
| Electrical conn | |
| Male/Female | Female |
| Electrical connection | Screwed cable entry |
| Electrical connection size | 2xPg 13.5 |
| Electrical connection standard | DIN 40430 |
| Electrical spec. standard | EN 60947-4/-5 |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.2-1.5 mm2 |
| Enclosure rating IP | IP66 |
| EU RoHS compliance | Yes |
| Max. sensor temperature [°C] | 100 °C |
| Max. sensor temperature [°F] | 212 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Reset function | Auto |
| Temperature range [°C] [max] | -15 °C |
| Temperature range [°C] [min] | -50 °C |
| Temperature range [°F] [max] | 5 °F |
| Temperature range [°F] [min] | -58 °F |
| Material | Room sensor |
| Temperature range | -50 to +70 degC (ambient); sensor -50 to -15 degC |
| IP rating | IP66 |
| Primary standard | EN 60947-5 |
| MOQ | 1 |
RT17 room sensor thermostat. Confirm setting range, reset type and sensor/capillary length against application.