Danfoss RT102 Thermostat 25 to 90 degC SPDT Auto Reset, 2 m capillary (017-514766)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
017-514766  ·  HS 9032.10
Danfoss RT102 Thermostat 25 to 90 degC SPDT Auto Reset, 2 m capillary (017-514766)

Danfoss RT102 mechanical temperature switch (thermostat) with capillary tube sensor and SPDT contact, auto reset. Sensor setting range 25 to 90 degC; differential 2.4 to 20 degC (adjustable); enclosure IP66. For industrial and marine refrigeration and HVAC applications. Danfoss code number 017-514766; EAN 5702423120376.

Technical Specifications

BrandDanfoss
ModelRT102 thermostat
Code number017-514766
Sensor temperature setting range25 to 90 degC
Differential2.4 to 20 degC (adjustable)
Contact functionSPDT
ResetAuto
Sensor typecapillary tube (averaging) sensor 4 x 1110 mm
Capillary tube length2000 mm (2 m)
Max. sensor temperature300 degC
EnclosureIP66
Ambient temperature range-50 to +70 degC
Cable entry2 x Pg 13.5
Contact ratingAC15=3 A, 400 V; AC1=10 A, 400 V; AC3=4 A, 400 V; DC13=12 W, 220 V; LR=28 A, 400 V
StandardsEN 60947-4, EN 60947-5
ApprovalsCCC, CE, EAC, LVD, RMRS, RoHS, RoHS China, TYSK
EAN5702423120376
Part number017-514766
Net weight0.948 Kilogram
TypeRT102
Product groupSwitches and thermostats
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalCCC
Cap. tube length fraction [in]78 3/4 in
Capillary tube length [mm]2000 mm
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Diff. @ Max. range setting[°C] [max]20 °C
Diff. @ Max. range setting[°C] [min]3.5 °C
Diff. @ Min. range setting[°C] [max]10 °C
Diff. @ Min. range setting[°C] [min]2.4 °C
Differential typeAdjustable
Electrical conn
Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2
Enclosure rating IPIP66
EU RoHS complianceYes
Max. sensor temperature [°C]300 °C
Max. sensor temperature [°F]572 °F
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Sensor size (Ø x L) [in]5/32 x 43 11/16 in
Sensor size (Ø x L) [mm]4 x 1110 mm
Temperature range [°C] [max]90 °C
Temperature range [°C] [min]25 °C
Temperature range [°F] [max]194 °F
Temperature range [°F] [min]77 °F

Properties

MaterialCapillary tube sensor
Temperature range-50 to +70 degC (ambient); sensor 25 to 90 degC
IP ratingIP66
Primary standardEN 60947-5
MOQ1

Compatibility

RT102 capillary tube sensor thermostat, 2 m capillary. Confirm setting range, reset type and sensor/capillary length against application.

Standards

Attached Documents