Danfoss RT101 Thermostat 25 to 90 °C SPDT Manual Max Reset, 2 m capillary (017-500466)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
017-500466  ·  HS 9032.10
Danfoss RT101 Thermostat 25 to 90 °C SPDT Manual Max Reset, 2 m capillary (017-500466)

Danfoss RT101 mechanical temperature switch (thermostat) with remote bulb sensor and single-pole double-throw (SPDT) contact, manual maximum reset. Sensor setting range 25 to 90 degC (77 to 194 degF) with 2000 mm (2 m) capillary; enclosure IP54. For industrial and marine applications. Danfoss code number 017-500466; EAN 5702423119455.

Technical Specifications

BrandDanfoss
ModelRT101 thermostat
Code number017-500466
Sensor temperature setting range25 to 90 degC (77 to 194 degF)
Differential2.4 to 4.1 degC (fixed)
Contact functionSPDT (single-pole double-throw)
ResetManual Max
Sensor typeremote bulb, sensor 9.5 x 80 mm
Capillary tube length2000 mm (2 m)
Max. sensor temperature300 degC (572 degF)
Chargeadsorption
EnclosureIP54
Ambient temperature range-50 to +70 degC (-58 to +158 degF)
Cable entry2 x Pg 13.5
Contact ratingAC15=3 A, 400 V; AC1=10 A, 400 V; AC3=4 A, 400 V; DC13=12 W, 220 V; LR=28 A, 400 V
StandardsEN 60947-4, EN 60947-5
ApprovalsBV, CCC, CE, CMIM, DNV, EAC, GL, LLC CDC EURO-TYSK, LVD, NKK, RMRS, RoHS, RoHS China, TYSK
EAN5702423119455
Part number017-500466
Net weight0.845 Kilogram
TypeRT101
Product groupSwitches and thermostats
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalBV
Cap. tube length fraction [in]78 3/4 in
Capillary tube length [mm]2000 mm
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Diff. @ Max. range setting[°C]4.1 °C
Diff. @ Min. range setting[°C]2.4 °C
Differential typeFixed
Electrical conn
Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2
Enclosure rating IPIP54
EU RoHS complianceYes
Max. sensor temperature [°C]300 °C
Max. sensor temperature [°F]572 °F
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionManual Max
Sensor pocket length min. [in]4 13/32 in
Sensor pocket length min. [mm]112 mm
Sensor size (Ø x L) [in]3/8 x 3 1/8 in
Sensor size (Ø x L) [mm]9.5 x 80 mm
Temperature range [°C] [max]90 °C
Temperature range [°C] [min]25 °C
Temperature range [°F] [max]194 °F
Temperature range [°F] [min]77 °F

Properties

MaterialRemote bulb sensor (adsorption charge)
Temperature range-50 to +70 degC (ambient); sensor 25 to 90 degC (77 to 194 degF)
IP ratingIP54
Primary standardEN 60947-5
MOQ1

Compatibility

RT101 remote-bulb thermostat, 2000 mm (2 m) capillary. Confirm setting range, reset type and capillary length against application.