cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-09
sales@cballast.com
cballast.com

Danfoss REG-SA 10 function module (Top Complete), fits SVL Flexline REG-SA 10 regulating valve, 65 bar (code 148B5761)

Danfoss · HVAC & Refrigeration · Globe Valves · Denmark · danfoss.com
Part Number
148B5761  ·  HS 8481.90
Danfoss REG-SA 10 function module (Top Complete), fits SVL Flexline REG-SA 10 regulating valve, 65 bar (code 148B5761)

Danfoss REG-SA 10 function module (also called Top Complete) for the SVL Flexline modular industrial-refrigeration valve platform, store code 148B5761. The function module is the complete field-serviceable operating top part — top part, one gasket and four bolts — that mounts on the matching REG-SA 10 regulating valve housing. A scaled spindle top gives repeatable manual throttling of liquid, suction, hot-gas and oil flow; the back-seating spindle lets the packing be serviced in operation. Flow area 3 mm2 (0.004 in2). It is the repair/replacement assembly, not a complete valve and not a loose gasket, so the regulating (throttling) function can be renewed without cutting the housing out of the line. For R717 (ammonia), R744 (CO2) and fluorinated refrigerants and their oils. Maximum working pressure 65 bar g (943 psig); media temperature -60 to 150 C (-76 to 302 F). net weight 0.208 kg, gross weight 0.455 kg. Specifications per Danfoss store code 148B5761.

Technical Specifications

TypeREG-SA 10 function module (Top Complete)
Code number148B5761
Fits valveSVL Flexline REG-SA 10 regulating valve
Functionregulating (throttling) operating top part
Parts includedtop part, 1 gasket, 4 bolts
Flow area3 mm2 (0.004 in2)
Maximum working pressure65 bar g (943 psig)
Media temperature range-60 to 150 C (-76 to 302 F)
Applicable mediaR717 (ammonia), R744 (CO2), HFC/HCFC refrigerants and oils
Weightnet weight 0.208 kg, gross weight 0.455 kg
ApprovalsCE
EAN5702428500746
Net weight0.208 Kilogram
Product groupShut-off and regulating valves
China RoHS complianceYes with exemptions
China RoHS exemption clause7.1
EquipmentCap
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(a)
Flow area [in2]0.004 in²
Flow area [mm2]3 mm²
Max. Working Pressure [bar]65 bar
Max. Working Pressure [psig]943 psig
NeckStandard
Outlet connection size [mm]10 mm
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR134a
Temperature range [°C] [max]150 °C
Temperature range [°C] [min]-60 °C
Temperature range [°F] [max]302 °F
Temperature range [°F] [min]-76 °F
Type designationTop Complete
Used for productREG-SA 10

Properties

MaterialSteel
Pressure rating65 bar
Temperature range-60 to 150 C
MOQ1

Compatibility

Danfoss SVL Flexline REG-SA 10 function module (Top Complete). Mounts on the matching REG-SA 10 valve housing / SVL multifunction valve body. Function modules are size-specific — confirm the housing nominal size class (10) before ordering. Shares the SVL Flexline platform with SVA-S/SVA-L shut-off, REG regulating and SCA-X/CHV-X check components of the same size.

Standards

Approvals

Attached Documents