Danfoss MSV-F2 DN 400 PN 16 flanged manual static balancing valve (003Z1091)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003Z1091  ·  HS 8481.80
Danfoss MSV-F2 DN 400 PN 16 flanged manual static balancing valve (003Z1091)

Danfoss MSV-F2 DN 400 PN 16 — flanged manual (static) double-regulating balancing valve for the main risers and branches of heating and cooling systems. Presetting the handwheel fixes the valve authority so design flow is distributed correctly across the network; the two built-in test plugs allow differential-pressure and flow measurement for commissioning without extra tappings, and the valve doubles as a shut-off. Kvs 2584.6 m³/h, maximum differential pressure 150 KPa, media temperature -10 °C to 130 °C, Cast iron (EN-GJL-250) body. OEM P/N 003Z1091. EAN 5702421557778. Technical data quoted verbatim from store.danfoss.com (code 003Z1091).

Technical Specifications

Code number003Z1091
TypeMSV-F2
Product groupManual balancing
DescriptionMSV-F2 DN 400 with test plugs PN16, manual balancing valve
Valve sizeDN 400
Valve body materialCast iron (EN-GJL-250)
Connection typesFlange
Test plugsWith test plugs
Setting scaleYes
Shut-off functionYes
Drain functionNo
Pressure classPN 16
Kvs values [m³/h]2584.6 m³/h
Differential pressure over the valve [kPa] [Max]150 KPa
Media temperature [°C] [Min]-10 °C
Media temperature [°C] [Max]130 °C
Contains batteriesNo
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
China RoHS complianceOut of scope
REACH Candidate List substancesLead (CAS no. 7439-92-1)
SCIP dossier no.2bc00472-4969-4f4a-bfc8-1c168f67534a
SCIP dossier product nameMSV-F2 DN200-DN400
Net weight834.5 Kilogram
Gross weight890 Kilogram
Volume1674.4 Liter
EAN5702421557778

Properties

MaterialValve body Cast iron (EN-GJL-250)
Pressure ratingPN 16
Temperature range-10 °C to 130 °C (media)
MOQ1

Compatibility

MSV-F2 is a static (manual) balancing valve — one per riser or branch. Select by pipe size (DN 400) and network pressure class (PN 16); use the Kvs (2584.6 m³/h) with the branch design flow to set the required presetting, and read the differential pressure across the two test plugs during commissioning. Pair with a Danfoss measuring instrument for flow read-out.