cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss MSV-F2 DN 200 flanged manual balancing valve PN 25 with test plugs (003Z1145)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003Z1145  ·  HS 8481.80
Danfoss MSV-F2 DN 200 flanged manual balancing valve PN 25 with test plugs (003Z1145)

Danfoss MSV-F2 DN 200 — flanged double-regulating manual balancing valve for the main risers and large branches of hydronic heating and cooling systems. The MSV-F2 sets and limits circuit flow by a lockable presetting on a graduated scale, with two self-sealing test plugs for differential-pressure/flow measurement and commissioning, and a full shut-off function. Body Ductile iron (EN-GJS 400-15), PN 25, Kvs 872 m³/h, flanged connection per EN 1092-1, media temperature -10 °C to 150 °C. OEM P/N 003Z1145. EAN 5715162497395. Technical data quoted verbatim from store.danfoss.com (code 003Z1145).

Technical Specifications

BrandDanfoss
Part number003Z1145
Code number003Z1145
TypeMSV-F2
Product groupManual balancing
DescriptionMSV-F2 DN 200 with test plugs PN25, manual balancing valve
Valve sizeDN 200
Valve body materialDuctile iron (EN-GJS 400-15)
Connection typesFlange
Pressure classPN 25
Kvs values [m³/h]872 m³/h
Media temperature [°C] [Min]-10 °C
Media temperature [°C] [Max]150 °C
Test plugsYes
Setting scaleYes
Drain functionNo
Shut-off functionYes
Contains batteriesNo
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
China RoHS complianceOut of scope
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Net weight98 Kilogram
Gross weight140 Kilogram
Volume644.16 Liter
EAN5715162497395
SCIP dossier no.b53622cd-50a2-4626-a23a-856f12c6983e
SCIP dossier product nameMSV-F2 MNF DN15-300
HS code8481.80

Properties

MaterialValve body Ductile iron (EN-GJS 400-15)
Pressure ratingPN 25
Temperature range-10 °C to 150 °C (media)
Standard sizeDN 200
MOQ1

Compatibility

Danfoss MSV-F2 DN 200 double-regulating balancing valve for PN 25 flanged pipework (EN 1092-1). Size the valve to the design flow and available head; use the graduated presetting scale to set flow and the two test plugs (supplied) for commissioning measurement. Pairs with a Danfoss PFM 4000 / partner measuring instrument for balancing.

Approvals