Danfoss MNF DN 50 PN 25 flanged manual static balancing valve (003Z1170)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003Z1170  ·  HS 8481.80
Danfoss MNF DN 50 PN 25 flanged manual static balancing valve (003Z1170)

Danfoss MNF DN 50 PN 25 — flanged manual (static) double-regulating balancing valve for the main risers and branches of heating and cooling systems. Presetting the handwheel fixes the valve authority so design flow is distributed correctly across the network; the two built-in test plugs allow differential-pressure and flow measurement for commissioning without extra tappings, and the valve doubles as a shut-off. Kvs 53.8 m³/h, maximum differential pressure 200 KPa, media temperature -10 °C to 130 °C, Ductile iron (EN-GJS 400-15) body. OEM P/N 003Z1170. EAN 5710104514628. Technical data quoted verbatim from store.danfoss.com (code 003Z1170).

Technical Specifications

Code number003Z1170
TypeMNF
Product groupManual balancing
DescriptionMNF DN 50 with test plugs PN25, manual balancing valve
Valve sizeDN 50
Valve body materialDuctile iron (EN-GJS 400-15)
Connection typesFlange
Test plugsWith test plugs
Setting scaleYes
Shut-off functionYes
Drain functionNo
Pressure classPN 25
Kvs values [m³/h]53.8 m³/h
Differential pressure over the valve [kPa] [Max]200 KPa
Media temperature [°C] [Min]-10 °C
Media temperature [°C] [Max]130 °C
Contains batteriesNo
REACH Candidate List substancesLead (CAS no. 7439-92-1)
SCIP dossier no.b53622cd-50a2-4626-a23a-856f12c6983e
SCIP dossier product nameMSV-F2 MNF DN15-300
Net weight8.585 Kilogram
Gross weight9.325 Kilogram
Volume14.535 Liter
EAN5710104514628

Properties

MaterialValve body Ductile iron (EN-GJS 400-15)
Pressure ratingPN 25
Temperature range-10 °C to 130 °C (media)
MOQ1

Compatibility

MNF is a static (manual) balancing valve — one per riser or branch. Select by pipe size (DN 50) and network pressure class (PN 25); use the Kvs (53.8 m³/h) with the branch design flow to set the required presetting, and read the differential pressure across the two test plugs during commissioning. Pair with a Danfoss measuring instrument for flow read-out.

Approvals

Attached Documents