cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss measuring orifice DN 500 PN 25 for hydronic balancing (003Z2286)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003Z2286  ·  HS 9026.90
Danfoss measuring orifice DN 500 PN 25 for hydronic balancing (003Z2286)

Danfoss measuring orifice DN 500 PN 25 — fixed calibrated orifice fitted in the pipe to create a defined pressure drop for flow measurement in hydronic balancing circuits, used with a balancing instrument to read circuit flow. Kvs 4230 m³/h. Suitable for PN 16/25/40 flange systems. OEM designation "Measuring orifice DN500 (PN25)". OEM P/N 003Z2286. EAN 5702420118017. Technical data quoted verbatim from store.danfoss.com (code 003Z2286).

Technical Specifications

Code number003Z2286
TypeMeasuring orifices
Product groupManual balancing
DescriptionMeasuring orifice DN500 (PN25)
SizeDN 500
Kvs value4230 m³/h
Pressure classPN 25
Contains batteriesNo
EU RoHS complianceOut of scope
China RoHS complianceOut of scope
Net weight23 Kilogram
Gross weight25 Kilogram
Volume51.263 Liter
EAN5702420118017
HS code9026.90
Kvs values [m³/h]4230 m³/h

Properties

Pressure ratingPN 25
Standard sizeMeasuring orifice
MOQ1

Compatibility

Select the orifice by pipe size (DN 500); the Kvs value fixes the flow/pressure-drop relation used to compute circuit flow with a differential-pressure measuring instrument. For large-diameter risers and mains where a measuring balancing valve is not fitted. Confirm DN and flange class before ordering.