Danfoss measuring orifice DN 150 PN 25 for hydronic balancing (003Z2279)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003Z2279  ·  HS 9026.90
Danfoss measuring orifice DN 150 PN 25 for hydronic balancing (003Z2279)

Danfoss measuring orifice DN 150 PN 25 — fixed calibrated orifice fitted in the pipe to create a defined pressure drop for flow measurement in hydronic balancing circuits, used with a balancing instrument to read circuit flow. Kvs 525 m³/h. Suitable for PN 16/25/40 flange systems. OEM designation "Measuring orifice DN150 (PN25+40)". OEM P/N 003Z2279. EAN 5702420117942. Technical data quoted verbatim from store.danfoss.com (code 003Z2279).

Technical Specifications

Code number003Z2279
TypeMeasuring orifices
Product groupManual balancing
DescriptionMeasuring orifice DN150 (PN25+40)
SizeDN 150
Kvs value525 m³/h
Pressure classPN 25
Contains batteriesNo
EU RoHS complianceYes with exemptions
China RoHS complianceOut of scope
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Net weight2.324 Kilogram
Gross weight4.518 Kilogram
Volume15.21 Liter
EAN5702420117942
HS code9026.90
EU RoHS exemption clause6(c)
Kvs values [m³/h]525 m³/h

Properties

Pressure ratingPN 25
Standard sizeMeasuring orifice
MOQ1

Compatibility

Select the orifice by pipe size (DN 150); the Kvs value fixes the flow/pressure-drop relation used to compute circuit flow with a differential-pressure measuring instrument. For large-diameter risers and mains where a measuring balancing valve is not fitted. Confirm DN and flange class before ordering.