Danfoss MBT 5252 heavy-duty temperature transmitter, code 084Z8217 (type designation MBT 5252-0011-0200-0200-G110). Terminal-box (Type B head) insertion temperature transmitter for cooling water, lubricating and hydraulic oil, and refrigeration plant in industrial and marine installations. Standardized Pt 100 platinum resistance element (100 ohm at 0 C), Class B tolerance per EN 60751. Insertion length 200 mm; G 1/2 male process connection (ISO 228-1-A). AISI 316 Ti stainless-steel protection tube, 10 mm. Measuring range -50 to +200 C (-58 to +392 F); output 4-20 mA (2-wire, loop-powered; 8-35 V DC supply). Type B terminal-box head, Pg 16; IP65 enclosure per IEC 60529. The measuring insert is exchangeable. Supplied in a 6-piece multipack. CE marked.
| Type | MBT 5252 heavy-duty temperature transmitter |
| Type designation | MBT 5252-0011-0200-0200-G110 |
| Code number | 084Z8217 |
| Sensor element | Pt 100 platinum resistance (100 ohm at 0 C) |
| Tolerance class | Class B per EN 60751 |
| Insertion length | 200 mm |
| Process connection | G 1/2 male, ISO 228-1-A |
| Protection tube | AISI 316 Ti stainless steel, 10 mm |
| Measuring range | -50 to +200 C (-58 to +392 F) |
| Output signal | 4-20 mA (2-wire, loop-powered; 8-35 V DC supply) |
| Supply voltage | 8-35 V DC (2-wire loop-powered) |
| Electrical connection | Type B terminal-box head, Pg 16 |
| Enclosure rating | IP65 per IEC 60529 |
| Net weight | 0.445 kg |
| Gross weight | 0.456 kg |
| Packing format | Multi pack (6 pc) |
| Approvals | CE |
| EAN | 5702423114245 |
| Product group | Sensors |
| Ambient temperature max. [°C] | 85 °C |
| Ambient temperature max. [°F] | 185 °F |
| Approval | CE |
| CE mark | Yes |
| China RoHS compliance | Out of scope |
| Connection material | Stainless steel |
| Connection standard | ISO 228 |
| Connection type | G |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical connection size | Pg 16 |
| Enclosure rating IP | IP65 |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(c) |
| Extension length [in] | 1.97 in |
| Extension length [mm] | 50 mm |
| In scope of WEEE | Yes |
| Insertion length [in] | 7.9 in |
| Insertion length [mm] | 200 mm |
| Insertion type | Fixed |
| Measuring range [°C] [max] | 100 °C |
| Measuring range [°C] [min] | 0 °C |
| Measuring range [°F] [max] | 212 °F |
| Measuring range [°F] [min] | 32 °F |
| Number of terminals [pcs] | 3 pc |
| Output signal [mA] [max] | 20 mA |
| Output signal [mA] [min] | 4 mA |
| Process connection Male/Female | Male |
| Process connection material | Stainless steel |
| Process connection size | 1/2 |
| Process connection standard | ISO 228-1-A |
| Process connection type | G |
| Protection tube diameter [in] | 0.394 in |
| Protection tube diameter [mm] | 10 mm |
| Protection tube material | AISI 316 TI |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Sensor elem. resistance [Ohm] | 100 Ohm |
| Sensor element [pc] | 1 pc |
| Sensor element standard | EN 60751 |
| Sensor element tolerance | Class B |
| Sensor element type | Pt |
| Sensor Insert | Exchangeable |
| Supply voltage [V] DC [max] | 35 V |
| Supply voltage [V] DC [min] | 8 V |
| Temperature range [°C] [max] | 200 °C |
| Temperature range [°C] [min] | -50 °C |
| Temperature range [°F] [max] | 392 °F |
| Temperature range [°F] [min] | -58 °F |
| Transmitter setting range [°C] [max] | 100 °C |
| Transmitter setting range [°C] [min] | 0 °C |
| Transmitter setting range [°F] [max] | 212 °F |
| Transmitter setting range [°F] [min] | 32 °F |
| Transmitter type | Standard |
| Wires [pcs] | 2 pc |
| Material | AISI 316 Ti stainless steel |
| Temperature range | -50 to +200 C |
| IP rating | IP65 |
| Standard size | 200 mm insertion |
| Thread standard | ISO 228-1-A |
| MOQ | 1 |
MBT 5252 insertion sensor with exchangeable measuring insert. Confirm the required insertion length (200 mm), process thread (G 1/2) and element type (Pt 100) match the thermowell/pocket and controller input before ordering. Factory-calibrated 4-20 mA output — confirm the measuring range matches the loop.