Danfoss MBT 5252 temperature transmitter, Pt 100, 50 mm insertion, G 1/2, 4-20 mA output (code 084Z6002)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
084Z6002  ·  HS 9025.19
Danfoss MBT 5252 temperature transmitter, Pt 100, 50 mm insertion, G 1/2, 4-20 mA output (code 084Z6002)

Danfoss MBT 5252 insertion temperature transmitter, code 084Z6002 (type designation MBT 5252-0011-0050-0200-G420). Integrated Pt 100 sensor and 2-wire loop-powered transmitter delivering a 4-20 mA output proportional to the measuring range, for cooling water, oil and refrigeration plant in general industry and marine installations. Pt 100 platinum element (100 ohm at 0 C), Class B tolerance per EN 60751. Insertion length 50 mm; G 1/2 male (ISO 228-1-A) process connection; AISI 316 Ti protection tube, 10 mm diameter. Measuring range -50 to +200 C (-58 to +392 F); 8-35 V DC supply; Type B connection head, Pg 16; IP65 enclosure per IEC 60529. CE marked.

Technical Specifications

TypeMBT 5252 (insertion temperature transmitter)
Type designationMBT 5252-0011-0050-0200-G420
Code number084Z6002
Sensor elementPt 100 platinum resistance (100 ohm at 0 C)
Tolerance classClass B per EN 60751
Insertion length50 mm
Process connectionG 1/2 male (ISO 228-1-A)
Protection tubeAISI 316 Ti stainless steel, 10 mm diameter
Measuring range-50 to +200 C (-58 to +392 F)
Output signal4-20 mA (2-wire, loop-powered)
Supply voltage8-35 V DC
Electrical connectionType B connection head, Pg 16
Enclosure ratingIP65 per IEC 60529
ApprovalsCE
EAN5702423123384
Net weight0.38 Kilogram
Product groupSensors
Ambient temperature max. [°C]85 °C
Ambient temperature max. [°F]185 °F
ApprovalCE
CE markYes
China RoHS complianceOut of scope
Connection materialStainless steel
Connection standardISO 228
Connection typeG
EEE category5 small equipment (any external dimension < 50 cm)
Electrical connection sizePg 16
Enclosure rating IPIP65
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Extension length [in]1.97 in
Extension length [mm]50 mm
In scope of WEEEYes
Insertion length [in]1.97 in
Insertion length [mm]50 mm
Insertion typeFixed
Measuring range [°C] [max]200 °C
Measuring range [°C] [min]-50 °C
Measuring range [°F] [max]392 °F
Measuring range [°F] [min]-58 °F
Number of terminals [pcs]3 pc
Output signal [mA] [max]20 mA
Output signal [mA] [min]4 mA
Process connection Male/FemaleMale
Process connection materialStainless steel
Process connection size1/2
Process connection standardISO 228-1-A
Process connection typeG
Protection tube diameter [in]0.394 in
Protection tube diameter [mm]10 mm
Protection tube materialAISI 316 TI
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Sensor elem. resistance [Ohm]100 Ohm
Sensor element [pc]1 pc
Sensor element standardEN 60751
Sensor element toleranceClass B
Sensor element typePt
Sensor InsertExchangeable
Supply voltage [V] DC [max]35 V
Supply voltage [V] DC [min]8 V
Temperature range [°C] [max]200 °C
Temperature range [°C] [min]-50 °C
Temperature range [°F] [max]392 °F
Temperature range [°F] [min]-58 °F
Transmitter setting range [°C] [max]200 °C
Transmitter setting range [°C] [min]-50 °C
Transmitter setting range [°F] [max]392 °F
Transmitter setting range [°F] [min]-58 °F
Transmitter typeStandard
Wires [pcs]2 pc

Properties

MaterialAISI 316 Ti stainless steel
Temperature range-50 to +200 C (-58 to +392 F)
IP ratingIP65
Standard size50 mm insertion
Thread standardISO 228-1-A
MOQ1

Compatibility

MBT 5252 transmitter (4-20 mA). Confirm the measuring range (-50 to +200 C (-58 to +392 F)) matches the receiving controller/PLC scaling and that a 8-35 V DC loop supply is available. Insertion 50 mm, G 1/2 thread.

Standards

Approvals