Danfoss MBT 3560 insertion temperature transmitter, code 084Z4100 (type designation MBT 3560-0001-0050-60-415). Compact temperature sensor with integrated 2-wire transmitter that converts the resistance of a built-in Pt 1000 platinum element into a standardized 4-20 mA (2-wire) signal, so a defined temperature span is transmitted directly without a separate head or rail transmitter. For engine cooling water, lubricating and hydraulic oil, compressor and HVAC/R circuits, and marine and industrial plant. Insertion length 50 mm; G 1/4 male process connection (ISO 228-1-A); AISI 316 Ti stainless-steel protection tube, 8 mm. Measuring range -50 to +200 C (-58 to +392 F). Output 4-20 mA (2-wire); supply 10-32 V DC. Electrical connection: M12 x 1, 4-pin (IEC 61076-2-101). IP65 enclosure per IEC 60529. Supplied in a 13-piece multipack. CE marked.
| Type | MBT 3560 temperature transmitter (sensor with built-in transmitter) |
| Type designation | MBT 3560-0001-0050-60-415 |
| Code number | 084Z4100 |
| Sensor element | Pt 1000 platinum resistance (1000 ohm at 0 C), EN 60751 |
| Measuring range | -50 to +200 C (-58 to +392 F) |
| Output signal | 4-20 mA (2-wire) |
| Supply voltage | 10-32 V DC |
| Insertion length | 50 mm |
| Process connection | G 1/4 male, ISO 228-1-A |
| Protection tube | AISI 316 Ti stainless steel, 8 mm dia. |
| Electrical connection | M12 x 1, 4-pin (IEC 61076-2-101) |
| Enclosure rating | IP65 per IEC 60529 |
| Net weight | 0.098 kg |
| Packing format | Multi pack (13 pc) |
| Approvals | CE |
| EAN | 5702423259496 |
| Product group | Sensors |
| Ambient temperature max. [°C] | 85 °C |
| Ambient temperature max. [°F] | 185 °F |
| Approval | CE |
| CE mark | Yes |
| China RoHS compliance | Out of scope |
| Connection material | Stainless steel |
| Connection standard | ISO 228 |
| Connection type | G |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical conn | |
| Male/Female | Male |
| Electrical connection size | 4 pin |
| Electrical connection standard | IEC 61076-2-101 |
| Enclosure rating IP | IP67 |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(c) |
| Extension length [in] | 1.3 in |
| Extension length [mm] | 33 mm |
| In scope of WEEE | Yes |
| Insertion length [in] | 1.97 in |
| Insertion length [mm] | 50 mm |
| Insertion type | Fixed |
| Measuring range [°C] [max] | 150 °C |
| Measuring range [°C] [min] | -50 °C |
| Measuring range [°F] [max] | 302 °F |
| Measuring range [°F] [min] | -58 °F |
| Output signal [mA] [max] | 20 mA |
| Output signal [mA] [min] | 4 mA |
| Process connection Male/Female | Male |
| Process connection material | Stainless steel |
| Process connection size | 1/4 |
| Process connection standard | ISO 228-1-A |
| Process connection type | G |
| Protection tube diameter [in] | 0.315 in |
| Protection tube diameter [mm] | 8 mm |
| Protection tube material | AISI 316 TI |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Sensor elem. resistance [Ohm] | 1000 Ohm |
| Sensor element [pc] | 1 pc |
| Sensor element tolerance | < ± 1% FS |
| Sensor element type | Pt |
| Sensor Insert | Fixed |
| Supply voltage [V] DC [max] | 32 V |
| Supply voltage [V] DC [min] | 10 V |
| Temperature range [°C] [max] | 200 °C |
| Temperature range [°C] [min] | -50 °C |
| Temperature range [°F] [max] | 392 °F |
| Temperature range [°F] [min] | -58 °F |
| Transmitter setting range [°C] [max] | 150 °C |
| Transmitter setting range [°C] [min] | -50 °C |
| Transmitter setting range [°F] [max] | 302 °F |
| Transmitter setting range [°F] [min] | -58 °F |
| Transmitter type | Integrated |
| Material | AISI 316 Ti stainless steel |
| Temperature range | -50 to +200 C |
| IP rating | IP65 |
| Standard size | 50 mm insertion |
| Thread standard | ISO 228-1-A |
| MOQ | 1 |
MBT 3560 sensor with factory built-in transmitter — the 4-20 mA (2-wire) span is preset by the type designation and is not field-rangeable on the standard version. Confirm the required insertion length (50 mm), process thread (G 1/4), output (4-20 mA (2-wire)) and supply (10-32 V DC) match the pocket/thermowell and controller input before ordering. A matching thermowell can be ordered separately.