cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss MBT 3560 temperature transmitter, Pt 1000, 4-20 mA (-50 to +200 C), 100 mm insertion, G 1/2 process connection, M12 4PIN (code 084Z4064)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
084Z4064  ·  HS 9025.19
Danfoss MBT 3560 temperature transmitter, Pt 1000, 4-20 mA (-50 to +200 C), 100 mm insertion, G 1/2 process connection, M12 4PIN (code 084Z4064)

Danfoss MBT 3560 insertion temperature transmitter, code 084Z4064 (type designation MBT 3560-0001-0100-62-420). Compact temperature sensor with an integrated 2-wire, loop-powered transmitter that converts the resistance of a built-in Pt 1000 platinum element into a standardized 4-20 mA signal, so a defined temperature is transmitted directly without a separate head or rail transmitter. For engine cooling water, lubricating and hydraulic oil, compressor, refrigeration and HVAC/R circuits, and marine and industrial plant. Insertion length 100 mm; G 1/2 male (ISO 228-1-A) process connection; AISI 316 Ti stainless-steel protection tube, 8 mm dia. Element measuring range -50 to +200 C (-58 to +392 F). Output 4-20 mA (2-wire) over a -50 to +200 C span; supply 10-32 V DC. Electrical connection: M12 x 1, 4-pin (IEC 61076-2-101). IP67 enclosure per IEC 60529. The built-in transmitter is factory-scaled to a -50 to +200 C output span. Supplied in a 13-piece multipack. CE marked.

Technical Specifications

TypeMBT 3560 temperature sensor with built-in transmitter
Type designationMBT 3560-0001-0100-62-420
Code number084Z4064
Sensor elementPt 1000 platinum resistance (1000 ohm at 0 C), EN 60751
Transmitter accuracy< ±1% FS
Measuring range (element)-50 to +200 C (-58 to +392 F)
Output signal4-20 mA (2-wire, loop-powered), transmitter setting range -50 to +200 C
Supply voltage10-32 V DC
Insertion length100 mm
Process connectionG 1/2 male (ISO 228-1-A)
Protection tubeAISI 316 Ti stainless steel, 8 mm dia.
Electrical connectionM12 x 1, 4-pin (IEC 61076-2-101)
Enclosure ratingIP67 per IEC 60529
Packing quantity13 pc (multipack)
Net weight0.145 kg
ApprovalsCE
EAN5702423227143
Product groupSensors
Ambient temperature max. [°C]85 °C
Ambient temperature max. [°F]185 °F
ApprovalCE
CE markYes
China RoHS complianceOut of scope
Connection materialStainless steel
Connection standardISO 228
Connection typeG
EEE category5 small equipment (any external dimension < 50 cm)
Electrical conn
Male/FemaleMale
Electrical connection size4 pin
Electrical connection standardIEC 61076-2-101
Enclosure rating IPIP67
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Extension length [in]1.3 in
Extension length [mm]33 mm
In scope of WEEEYes
Insertion length [in]3.94 in
Insertion length [mm]100 mm
Insertion typeFixed
Measuring range [°C] [max]200 °C
Measuring range [°C] [min]-50 °C
Measuring range [°F] [max]392 °F
Measuring range [°F] [min]-58 °F
Output signal [mA] [max]20 mA
Output signal [mA] [min]4 mA
Process connection Male/FemaleMale
Process connection materialStainless steel
Process connection size1/2
Process connection standardISO 228-1-A
Process connection typeG
Protection tube diameter [in]0.315 in
Protection tube diameter [mm]8 mm
Protection tube materialAISI 316 TI
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Sensor elem. resistance [Ohm]1000 Ohm
Sensor element [pc]1 pc
Sensor element tolerance< ± 1% FS
Sensor element typePt
Sensor InsertFixed
Supply voltage [V] DC [max]32 V
Supply voltage [V] DC [min]10 V
Temperature range [°C] [max]200 °C
Temperature range [°C] [min]-50 °C
Temperature range [°F] [max]392 °F
Temperature range [°F] [min]-58 °F
Transmitter setting range [°C] [max]200 °C
Transmitter setting range [°C] [min]-50 °C
Transmitter setting range [°F] [max]392 °F
Transmitter setting range [°F] [min]-58 °F
Transmitter typeIntegrated

Properties

MaterialAISI 316 Ti stainless steel
Temperature range-50 to +200 C (-58 to +392 F)
IP ratingIP67
Standard size100 mm insertion
Thread standardISO 228-1-A
MOQ1

Compatibility

MBT 3560 sensor with factory built-in transmitter — the 4-20 mA (2-wire) -50 to +200 C span is preset by the type designation and is not field-rangeable on the standard version. Confirm the required insertion length (100 mm), process thread (G 1/2), electrical connector and supply match the pocket/thermowell and controller input before ordering. A matching thermowell can be ordered separately.

Standards

Approvals