Danfoss KPS76 marine thermostat, code 060L311266. Regulating range -10 to 30 °C (14 to 86 °F) via rigid (direct-mounted) sensor. Differential 3 to 10 K, adjustable; automatic reset; SPDT gold snap-action contact. Enclosure IP67; ambient -40 to +70 °C; maximum sensor temperature 80 °C (176 °F). Enamelled pressure die-cast aluminium (GD-AlSi 12) housing. For temperature monitoring, control and limit protection of non-aggressive media. Carries marine type approval (ABS/BV/DNV/GL/LR/NKK/RINA/RMRS). EAN 5702423147663.
| Type | KPS76 thermostat |
| Code number | 060L311266 |
| Setting (regulating) range | -10 to 30 °C (14 to 86 °F) |
| Differential | 3 to 10 K (adjustable, min. range) |
| Reset | Automatic |
| Contact system | SPDT gold |
| Sensor | remote bulb |
| Sensor size | Ø13 × 63 mm |
| Capillary tube length | 2000 mm |
| Sensor pocket length (min.) | 75 mm |
| Max. sensor temperature | 80 °C (176 °F) |
| Enclosure | IP67 |
| Ambient temperature | -40 to +70 °C |
| Electrical connection | Screwed cable entry, Pg 13.5 (DIN 40430) |
| Connection for pocket | M 18 × 1.5 |
| Contact rating | AC15=4 A/440 V; AC1=10 A/440 V; AC3=6 A/440 V; DC13=12 W/220 V; gold contacts 1–30 mA/5–30 V |
| Approvals | CE, EAC, CCC, CCS, UL, ABS, BV, DNV, GL, LR, NKK, RINA, RMRS, LVD |
| EAN | 5702423147663 |
| Net weight | 1.158 Kilogram |
| Product group | Switches and thermostats |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [max] | 70 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 158 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Approval | ABS |
| Armoring | Yes |
| Cap. tube length fraction [in] | 78 3/4 in |
| Capillary tube length [mm] | 2000 mm |
| CE mark | Yes |
| Charge type | Adsorption |
| China RoHS compliance | Yes |
| Connection for pocket or hose | M 18 x 1.5 |
| Contact function | SPDT gold |
| Diff. @ Min. range setting [K] [max] | 10 K |
| Diff. @ Min. range setting [K] [min] | 3 K |
| Diff. @ Min. range setting[°C] [max] | 10 °C |
| Diff. @ Min. range setting[°C] [min] | 3 °C |
| Differential type | Adjustable |
| Electrical conn. comments | Metal cable gland |
| Electrical conn | |
| Male/Female | Female |
| Electrical connection size | Pg 13.5 |
| Electrical connection standard | DIN 40430 |
| Electrical spec. standard | EN 60947-5 |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2 |
| Enclosure rating IP | IP67 |
| Equipment | Armored cap. tube |
| EU RoHS compliance | Out of scope |
| Max. sensor temperature [°C] | 80 °C |
| Max. sensor temperature [°F] | 176 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Reset function | Auto |
| Sensor pocket length min. [in] | 3 in |
| Sensor pocket length min. [mm] | 75 mm |
| Sensor size (Ø x L) [in] | 1/2 x 2 1/2 in |
| Sensor size (Ø x L) [mm] | 13 x 63 mm |
| Sensor type | Remote bulb |
| Temperature range [°C] [max] | 30 °C |
| Temperature range [°C] [min] | -10 °C |
| Temperature range [°F] [max] | 86 °F |
| Temperature range [°F] [min] | 14 °F |
| UL approval file name | E73170 |
| UL mark | Yes |
| Material | remote bulb sensor with enamelled die-cast aluminium housing and steel capillary |
| Temperature range | -40 to +70 °C |
| IP rating | IP67 |
| MOQ | 1 |
KPS76 marine temperature switch (IP67, remote bulb sensor) for temperature regulation and limit/overheat protection on ships, compressors and large machinery. Contact wired NO or NC. Verify regulating range (-10 to 30 °C), sensor length and pocket before ordering.