cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KPR5 pressure switch, 6 to 18 bar, narrow 1-2.5 bar differential, auto reset, SPDT, 1/4 in flare

Danfoss · Sensors & Instrumentation · Pressure Switches · Denmark · danfoss.com
Part Number
060-117466  ·  HS 9026.20
Danfoss KPR5 pressure switch, 6 to 18 bar, narrow 1-2.5 bar differential, auto reset, SPDT, 1/4 in flare

Danfoss KPR5 pressure switch, code 060-117466. Regulating range 6 to 18 bar with a narrow differential of 1 to 2.5 bar, automatic reset, SPDT contact. 1/4 in flare (male) pressure connection, IP30 enclosure, max working pressure 20 bar. Close-differential KPR member of the KP family for condensing-pressure / capacity regulation. Bellows pressure element. CE / LVD marked.

Technical Specifications

TypeKPR5 pressure switch
Code number060-117466
Regulating range6 to 18 bar
Differential range1 to 2.5 bar
Resetautomatic
Contact systemSPDT
Connection1/4 in flare, male
Max working pressure20 bar
EnclosureIP30
ApprovalsCE, LVD
EAN5702428011839
Product groupSwitches and thermostats
Max. test pressure319.0 psig
Max. test pressure Pe22.0 bar
Ambient temperature range-40 °C to 65 °C
RefrigerantsR113; R1233zd(E); R124; R134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R438A; R448A; R449A; R449B; R450A; R452A; R507A; R513A
Lubricants compatibilityOilfree applications
UL approved refrigerantsR113; R124; R134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R438A; R448A; R449A; R449B; R450A; R452A; R507A; R513A
CE markYes
REACH candidate-list substancesLead (CAS no. 7439-92-1); Cadmium oxide (CAS no.1306-19-0)
Net weight0.297 kg
Amb
Temp
Note80 °C/176 °F for max 120 min
Contact functionSPDT
Contact ratingAC15=4 A, 440 V; AC1=10 A, 440 V; AC3=6 A, 440 V; DC13=12 W, 220 V; LR=36 A, 240 V; LR=48 A, 120 V
Differential1.00 bar to 2.50 bar
Electrical connectionRubber cable gland
Electrical connection size6-14 mm
EN 60947 electrical propertiesInsulation: 400V; Pollution degree: 3; Rated impulse voltage: 4 kV; Short circuit prot, fuse: 16A
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2; Flex, no ferrules: 0.7-2.5 mm2; Solid/stranded: 0.75-2.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
Identical product060-514266
Oil free refrigerantsR134a; R513A; R515B
Pressure connection size1/4
Pressure connection standardDIN 8906
Pressure connection typeFlare
Pressure Male/FemaleMale
Pressure sensing elementBellows
Regulation range Pe6.00 bar to 18.00 bar
Reset functionAuto

Properties

MaterialSteel/zinc-plated housing; bellows pressure element
Pressure ratingmax working pressure 20 bar
Temperature range-40 to +65 °C
IP ratingIP30
Thread standard1/4 in flare, male
MOQ1

Compatibility

Condensing-pressure / capacity regulation requiring a close on-off differential; automatic reset. KPR close-differential variant of KP5.

Standards

Approvals

Attached Documents