cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KP98 thermostat, 60 to 120 °C, manual reset, remote bulb

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L202466  ·  HS 9032.10
Danfoss KP98 thermostat, 60 to 120 °C, manual reset, remote bulb

Danfoss KP98 thermostat, code 060L202466. Sensor (regulating) range 60 to 120 °C (left) / 100 to 180 °C (right) (140 to 250 °F / 210 to 350 °F) via remote bulb, 1016 mm capillary tube. Differential 14 K (fixed); manual reset (maximum); 2 x SPST(NC); 16 A at 120 V ac / 8 A at 240 V ac (single phase) snap-action contact. Enclosure IP30; ambient -40 to +65 °C. Carries marine type approval (RINA/RMRS). For temperature monitoring, control and limit protection of non-aggressive media. EAN 5702428016797.

Technical Specifications

TypeKP98 thermostat
Code number060L202466
Sensor (regulating) range60 to 120 °C (left) / 100 to 180 °C (right) (140 to 250 °F / 210 to 350 °F)
Differential14 K (fixed)
ResetManual reset (maximum)
Contact system2 x SPST(NC); 16 A at 120 V ac / 8 A at 240 V ac (single phase)
Sensorremote bulb
Capillary tube length1016 mm
EnclosureIP30
Ambient temperature-40 to +65 °C
Electrical connectionrubber cable gland
ApprovalsCE, EAC, CCC, UL, CSA, RINA, RMRS, LVD, CMIM
EAN5702428016797
Net weight0.62 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCCC
Cap. tube length fraction [in]40 in
Capillary tube length [mm]1016 mm
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Contact function2 SPST(NC)
Contact rating120 V ac, 16 FLA, 96 LRA
Diff. @ Max. range setting [K]14 K
Diff. @ Max. range setting[°C]14 °C
Diff. @ Max. range setting[°F]25 °F
Diff. @ Min. range setting [K]14 K
Diff. @ Min. range setting[°C]14 °C
Diff. @ Min. range setting[°F]25 °F
Differential typeFixed
Electrical conn
Male/FemaleFemale
Electrical connection sizeNPSM 1/2 - 14
Electrical connection standardANSI/ASME B1.20.1
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EquipmentRight side cap.tube 80 in
EU RoHS complianceYes
Max. sensor temperature [°C]150 °C
Max. sensor temperature [°F]302 °F
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionManual Max
Reset function, left sideManual Max
Reset function, right sideManual Max
Sensor size (Ø x L) [in]3/8 x 4 1/2 in
Sensor size (Ø x L) [mm]9.5 x 115 mm
Sensor typeRemote bulb
Temp. range left side [°C] [max]120 °C
Temp. range left side [°C] [min]60 °C
Temp. range left side [°F] [max]250 °F
Temp. range left side [°F] [min]140 °F
Temp. range right side [°C] [max]180 °C
Temp. range right side [°C] [min]100 °C
Temp. range right side [°F] [max]350 °F
Temp. range right side [°F] [min]210 °F
UL approval file nameE31024
UL markYes

Properties

Materialremote bulb with steel housing
Temperature range-40 to +65 °C
IP ratingIP30
MOQ1

Compatibility

KP98 temperature switch for HVAC-R temperature regulation and limit/frost/overheat protection. Contact wired NO or NC. Verify regulating range (60 to 120 °C) and differential against the set point before ordering.

Standards

Approvals

Attached Documents