Danfoss KP98 thermostat, 60 to 120 °C / 100 to 180 °C (dual range), manual (maximum) reset, 2 x SPST, remote bulb 9.5 x 115 mm

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L113166  ·  HS 9032.10
Danfoss KP98 thermostat, 60 to 120 °C / 100 to 180 °C (dual range), manual (maximum) reset, 2 x SPST, remote bulb 9.5 x 115 mm

Danfoss KP98 thermostat, code 060L113166. Sensor (regulating) range 60 to 120 °C / 100 to 180 °C (dual range) (140 to 250 °F / 210 to 350 °F) via remote bulb 9.5 x 115 mm with 1000 mm capillary tube. Differential 14 K (fixed, both range settings); manual (maximum) reset; 2 x SPST (NC) (dual single-pole normally-closed) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 150 °C. For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702428016490.

Technical Specifications

TypeKP98 thermostat
Code number060L113166
Sensor (regulating) range60 to 120 °C / 100 to 180 °C (dual range) (140 to 250 °F / 210 to 350 °F)
Differential14 K (fixed, both range settings)
ResetManual (maximum) reset
Contact system2 x SPST (NC) (dual single-pole normally-closed)
Contact ratingAC15 10 A 400 V; AC1 16 A 400 V
Sensorremote bulb 9.5 x 115 mm
Capillary tube length1000 mm
Maximum sensor temperature150 °C
EnclosureIP30
Ambient temperature-40 to +65 °C (80 °C for max 120 min)
Electrical connectionrubber cable gland 6-14 mm
ApprovalsCE, UL, CCC, EAC
EAN5702428016490
Net weight0.62 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCCC
Cap. tube length fraction [in]39 3/8 in
Capillary tube length [mm]1000 mm
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Contact function2 SPST(NC)
Diff. @ Max. range setting [K]14 K
Diff. @ Max. range setting[°C]14 °C
Diff. @ Min. range setting [K]14 K
Diff. @ Min. range setting[°C]14 °C
Differential typeFixed
Electrical connection size6-14 mm
Electrical spec. standardEN 60947-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EquipmentRight side cap.tube 2 m
EU RoHS complianceYes
Max. sensor temperature [°C]150 °C
Max. sensor temperature [°F]302 °F
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionManual Max
Reset function, left sideManual Max
Reset function, right sideManual Max
Sensor size (Ø x L) [in]3/8 x 4 1/2 in
Sensor size (Ø x L) [mm]9.5 x 115 mm
Sensor typeRemote bulb
Temp. range left side [°C] [max]120 °C
Temp. range left side [°C] [min]60 °C
Temp. range left side [°F] [max]250 °F
Temp. range left side [°F] [min]140 °F
Temp. range right side [°C] [max]180 °C
Temp. range right side [°C] [min]100 °C
Temp. range right side [°F] [max]350 °F
Temp. range right side [°F] [min]210 °F
UL approval file nameE31024
UL markYes

Properties

MaterialRemote bulb with steel housing
Temperature range-40 to +65 °C (80 °C for max 120 min)
IP ratingIP30
MOQ1

Compatibility

KP98 temperature switch for HVAC-R temperature regulation and frost/overheat protection. SPDT contact wired NO or NC. Verify regulating range (60 to 120 °C / 100 to 180 °C (dual range)) and differential against the set point before ordering.

Standards

Approvals

Attached Documents