Danfoss KP98 thermostat, code 060L113166. Sensor (regulating) range 60 to 120 °C / 100 to 180 °C (dual range) (140 to 250 °F / 210 to 350 °F) via remote bulb 9.5 x 115 mm with 1000 mm capillary tube. Differential 14 K (fixed, both range settings); manual (maximum) reset; 2 x SPST (NC) (dual single-pole normally-closed) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 150 °C. For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702428016490.
| Type | KP98 thermostat |
| Code number | 060L113166 |
| Sensor (regulating) range | 60 to 120 °C / 100 to 180 °C (dual range) (140 to 250 °F / 210 to 350 °F) |
| Differential | 14 K (fixed, both range settings) |
| Reset | Manual (maximum) reset |
| Contact system | 2 x SPST (NC) (dual single-pole normally-closed) |
| Contact rating | AC15 10 A 400 V; AC1 16 A 400 V |
| Sensor | remote bulb 9.5 x 115 mm |
| Capillary tube length | 1000 mm |
| Maximum sensor temperature | 150 °C |
| Enclosure | IP30 |
| Ambient temperature | -40 to +65 °C (80 °C for max 120 min) |
| Electrical connection | rubber cable gland 6-14 mm |
| Approvals | CE, UL, CCC, EAC |
| EAN | 5702428016490 |
| Net weight | 0.62 Kilogram |
| Product group | Switches and thermostats |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [max] | 65 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 150 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Approval | CCC |
| Cap. tube length fraction [in] | 39 3/8 in |
| Capillary tube length [mm] | 1000 mm |
| CE mark | Yes |
| Charge type | Adsorption |
| China RoHS compliance | Yes |
| Contact function | 2 SPST(NC) |
| Diff. @ Max. range setting [K] | 14 K |
| Diff. @ Max. range setting[°C] | 14 °C |
| Diff. @ Min. range setting [K] | 14 K |
| Diff. @ Min. range setting[°C] | 14 °C |
| Differential type | Fixed |
| Electrical connection size | 6-14 mm |
| Electrical spec. standard | EN 60947-5 |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2 |
| Enclosure rating IP | IP30 |
| Enclosure rating Nema (~) | 1 |
| Equipment | Right side cap.tube 2 m |
| EU RoHS compliance | Yes |
| Max. sensor temperature [°C] | 150 °C |
| Max. sensor temperature [°F] | 302 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Reset function | Manual Max |
| Reset function, left side | Manual Max |
| Reset function, right side | Manual Max |
| Sensor size (Ø x L) [in] | 3/8 x 4 1/2 in |
| Sensor size (Ø x L) [mm] | 9.5 x 115 mm |
| Sensor type | Remote bulb |
| Temp. range left side [°C] [max] | 120 °C |
| Temp. range left side [°C] [min] | 60 °C |
| Temp. range left side [°F] [max] | 250 °F |
| Temp. range left side [°F] [min] | 140 °F |
| Temp. range right side [°C] [max] | 180 °C |
| Temp. range right side [°C] [min] | 100 °C |
| Temp. range right side [°F] [max] | 350 °F |
| Temp. range right side [°F] [min] | 210 °F |
| UL approval file name | E31024 |
| UL mark | Yes |
| Material | Remote bulb with steel housing |
| Temperature range | -40 to +65 °C (80 °C for max 120 min) |
| IP rating | IP30 |
| MOQ | 1 |
KP98 temperature switch for HVAC-R temperature regulation and frost/overheat protection. SPDT contact wired NO or NC. Verify regulating range (60 to 120 °C / 100 to 180 °C (dual range)) and differential against the set point before ordering.