cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KP78 thermostat, 30 to 90 °C, automatic, SPDT, remote bulb 9.5 x 85 mm

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L118466  ·  HS 9032.10
Danfoss KP78 thermostat, 30 to 90 °C, automatic, SPDT, remote bulb 9.5 x 85 mm

Danfoss KP78 thermostat, code 060L118466. Sensor (regulating) range 30 to 90 °C (86 to 194 °F) via remote bulb 9.5 x 85 mm with 2000 mm capillary tube. Differential 7 to 16.5 K (max range setting); 4.5 to 20 K (min range setting), adjustable; automatic; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 150 °C. For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702423148783.

Technical Specifications

TypeKP78 thermostat
Code number060L118466
Sensor (regulating) range30 to 90 °C (86 to 194 °F)
Differential7 to 16.5 K (max range setting); 4.5 to 20 K (min range setting), adjustable
ResetAutomatic
Contact systemSPDT (single-pole double-throw)
Contact ratingAC15 10 A 400 V; AC1 16 A 400 V; AC3 16 A 400 V; DC13 12 W 220 V; LR 112 A 400 V
Sensorremote bulb 9.5 x 85 mm
Capillary tube length2000 mm
Maximum sensor temperature150 °C
EnclosureIP30
Ambient temperature-40 to +65 °C (80 °C for max 120 min)
Electrical connectionrubber cable gland 6-14 mm
ApprovalsCE, UL, CCC, EAC
EAN5702423148783
Net weight0.408 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCCC
Cap. tube length fraction [in]78 3/4 in
Capillary tube length [mm]2000 mm
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Contact functionSPDT
Diff. @ Max. range setting [K] [max]16.5 K
Diff. @ Max. range setting [K] [min]7 K
Diff. @ Max. range setting[°C] [max]16.5 °C
Diff. @ Max. range setting[°C] [min]7 °C
Diff. @ Min. range setting [K] [max]20 K
Diff. @ Min. range setting [K] [min]4.5 K
Diff. @ Min. range setting[°C] [max]20 °C
Diff. @ Min. range setting[°C] [min]4.5 °C
Differential typeAdjustable
Electrical connection size6-14 mm
Electrical spec. standardEN 60947-5
EN 60947 electrical propertiesPollution degree: 3
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EU RoHS complianceYes
Max. sensor temperature [°C]150 °C
Max. sensor temperature [°F]302 °F
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Sensor size (Ø x L) [in]3/8 x 3 3/8 in
Sensor size (Ø x L) [mm]9.5 x 85 mm
Sensor typeRemote bulb
Temperature range [°C] [max]90 °C
Temperature range [°C] [min]30 °C
Temperature range [°F] [max]194 °F
Temperature range [°F] [min]86 °F
UL approval file nameE31024
UL markYes

Properties

MaterialRemote bulb with steel housing
Temperature range-40 to +65 °C (80 °C for max 120 min)
IP ratingIP30
MOQ1

Compatibility

KP78 temperature switch for HVAC-R temperature regulation and frost/overheat protection. SPDT contact wired NO or NC. Verify regulating range (30 to 90 °C) and differential against the set point before ordering.

Standards

Approvals

Attached Documents