Danfoss KP75 thermostat, code 060L112066. Sensor (regulating) range 0 to 35 °C (32 to 95 °F) via remote duct sensor 25 x 125 mm with 2000 mm capillary tube. Differential 2.5 to 12 K (max range setting); 3.5 to 16 K (min range setting), adjustable; automatic; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 110 °C. Carries marine type approval (DNV/BV/GL/LR/RINA/RMRS). For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702428016469.
| Type | KP75 thermostat |
| Code number | 060L112066 |
| Sensor (regulating) range | 0 to 35 °C (32 to 95 °F) |
| Differential | 2.5 to 12 K (max range setting); 3.5 to 16 K (min range setting), adjustable |
| Reset | Automatic |
| Contact system | SPDT (single-pole double-throw) |
| Contact rating | AC15 10 A 400 V; AC1 16 A 400 V; AC3 16 A 400 V; DC13 12 W 220 V; LR 112 A 400 V |
| Sensor | remote duct sensor 25 x 125 mm |
| Capillary tube length | 2000 mm |
| Maximum sensor temperature | 110 °C |
| Enclosure | IP30 |
| Ambient temperature | -40 to +65 °C (80 °C for max 120 min) |
| Electrical connection | rubber cable gland 6-14 mm |
| Approvals | CE, EAC, CCC, UL, CSA, DNV, BV, GL, LR, RINA, RMRS, LVD, CMIM |
| EAN | 5702428016469 |
| Net weight | 0.462 Kilogram |
| Product group | Switches and thermostats |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [max] | 65 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 150 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Approval | BV |
| Cap. tube length fraction [in] | 78 3/4 in |
| Capillary tube length [mm] | 2000 mm |
| CE mark | Yes |
| Charge type | Adsorption |
| China RoHS compliance | Yes |
| Contact function | SPDT |
| Diff. @ Max. range setting [K] [max] | 12 K |
| Diff. @ Max. range setting [K] [min] | 2.5 K |
| Diff. @ Max. range setting[°C] [max] | 12 °C |
| Diff. @ Max. range setting[°C] [min] | 2.5 °C |
| Diff. @ Min. range setting [K] [max] | 16 K |
| Diff. @ Min. range setting [K] [min] | 3.5 K |
| Diff. @ Min. range setting[°C] [max] | 16 °C |
| Diff. @ Min. range setting[°C] [min] | 3.5 °C |
| Differential type | Adjustable |
| Electrical connection size | 6-14 mm |
| Electrical spec. standard | EN 60947-5 |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2 |
| Enclosure rating IP | IP30 |
| Enclosure rating Nema (~) | 1 |
| EU RoHS compliance | Yes |
| Max. sensor temperature [°C] | 110 °C |
| Max. sensor temperature [°F] | 230 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Reset function | Auto |
| Sensor size (Ø x L) [in] | 1 x 3 5/8 in |
| Sensor size (Ø x L) [mm] | 25 x 125 mm |
| Sensor type | Remote duct sensor |
| Temperature range [°C] [max] | 35 °C |
| Temperature range [°C] [min] | 0 °C |
| Temperature range [°F] [max] | 95 °F |
| Temperature range [°F] [min] | 32 °F |
| UL approval file name | E31024 |
| UL mark | Yes |
| Material | Remote duct sensor with steel housing |
| Temperature range | -40 to +65 °C (80 °C for max 120 min) |
| IP rating | IP30 |
| MOQ | 1 |