Danfoss KP63 thermostat, -50 to 10 °C, automatic, SPDT, remote air coil 9.5 x 70 mm

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L110866  ·  HS 9032.10
Danfoss KP63 thermostat, -50 to 10 °C, automatic, SPDT, remote air coil 9.5 x 70 mm

Danfoss KP63 thermostat, code 060L110866. Sensor (regulating) range -50 to 10 °C (-58 to 14 °F) via remote air coil 9.5 x 70 mm with 2000 mm capillary tube. Differential 2.7 to 8 K (max range setting); 10 to 70 K (min range setting), adjustable; automatic; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 120 °C. Carries marine type approval (DNV/BV/GL/LR/RINA/RMRS). For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702428014557.

Technical Specifications

TypeKP63 thermostat
Code number060L110866
Sensor (regulating) range-50 to 10 °C (-58 to 14 °F)
Differential2.7 to 8 K (max range setting); 10 to 70 K (min range setting), adjustable
ResetAutomatic
Contact systemSPDT (single-pole double-throw)
Contact ratingAC15 10 A 400 V; AC1 16 A 400 V; AC3 16 A 400 V; DC13 12 W 220 V; LR 112 A 400 V
Sensorremote air coil 9.5 x 70 mm
Capillary tube length2000 mm
Maximum sensor temperature120 °C
EnclosureIP30
Ambient temperature-40 to +65 °C (80 °C for max 120 min)
Electrical connectionrubber cable gland 6-14 mm
ApprovalsCE, EAC, CCC, UL, CSA, DNV, BV, GL, LR, RINA, RMRS, LVD, CMIM
EAN5702428014557
Net weight0.366 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalBV
Cap. tube length fraction [in]78 3/4 in
Capillary tube length [mm]2000 mm
CE markYes
Charge typeVapour
China RoHS complianceYes
Contact functionSPDT
Diff. @ Max. range setting [K] [max]8 K
Diff. @ Max. range setting [K] [min]2.7 K
Diff. @ Max. range setting[°C] [max]8 °C
Diff. @ Max. range setting[°C] [min]2.7 °C
Diff. @ Min. range setting [K] [max]70 K
Diff. @ Min. range setting [K] [min]10 K
Diff. @ Min. range setting[°C] [max]70 °C
Diff. @ Min. range setting[°C] [min]10 °C
Differential typeAdjustable
Electrical connection size6-14 mm
Electrical spec. standardEN 60947-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EU RoHS complianceYes
Max. sensor temperature [°C]120 °C
Max. sensor temperature [°F]248 °F
Other RoHS documentationSaudi Arabia RoHS
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Sensor size (Ø x L) [in]3/8 x 2 3/4 in
Sensor size (Ø x L) [mm]9.5 x 70 mm
Sensor typeRemote air coil
Temperature range [°C] [max]10 °C
Temperature range [°C] [min]-50 °C
Temperature range [°F] [max]14 °F
Temperature range [°F] [min]-58 °F
UL approval file nameE31024
UL markYes

Properties

MaterialRemote air coil with steel housing
Temperature range-40 to +65 °C (80 °C for max 120 min)
IP ratingIP30
MOQ1

Compatibility

KP63 temperature switch for HVAC-R temperature regulation and frost/overheat protection. SPDT contact wired NO or NC. Verify regulating range (-50 to 10 °C) and differential against the set point before ordering.

Standards

Approvals