Danfoss KP61 thermostat, -30 to 15 °C, automatic reset, capillary (contact) sensor

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L200066  ·  HS 9032.10
Danfoss KP61 thermostat, -30 to 15 °C, automatic reset, capillary (contact) sensor

Danfoss KP61 thermostat, code 060L200066. Sensor (regulating) range -30 to 15 °C (-22 to 59 °F) via capillary (contact) sensor, 2030 mm capillary tube. Differential 1.5 to 23 K (adjustable, depending on range setting); automatic; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30; ambient -40 to +65 °C. Carries marine type approval (DNV/BV/GL/LR/RINA/RMRS). For temperature monitoring, control and limit protection of non-aggressive media. EAN 5702428014922.

Technical Specifications

TypeKP61 thermostat
Code number060L200066
Sensor (regulating) range-30 to 15 °C (-22 to 59 °F)
Differential1.5 to 23 K (adjustable, depending on range setting)
ResetAutomatic
Contact systemSPDT (single-pole double-throw)
Sensorcapillary (contact) sensor
Capillary tube length2030 mm
EnclosureIP30
Ambient temperature-40 to +65 °C
Electrical connectionrubber cable gland
ApprovalsCE, EAC, CCC, UL, CSA, DNV, BV, GL, LR, RINA, RMRS, LVD, CMIM
EAN5702428014922
Net weight0.4 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalBV
Cap. tube length fraction [in]80 in
Capillary tube length [mm]2030 mm
CE markYes
Charge typeVapour
China RoHS complianceYes
Contact functionSPDT
Contact rating120 V ac, 16 FLA, 96 LRA
Diff. @ Max. range setting [K] [max]7 K
Diff. @ Max. range setting [K] [min]1.5 K
Diff. @ Max. range setting[°C] [max]7 °C
Diff. @ Max. range setting[°C] [min]1.5 °C
Diff. @ Max. range setting[°F] [max]13 °F
Diff. @ Max. range setting[°F] [min]2.5 °F
Diff. @ Min. range setting [K] [max]23 K
Diff. @ Min. range setting [K] [min]5.5 K
Diff. @ Min. range setting[°C] [max]23 °C
Diff. @ Min. range setting[°C] [min]5.5 °C
Diff. @ Min. range setting[°F] [max]40 °F
Diff. @ Min. range setting[°F] [min]10 °F
Differential typeAdjustable
Electrical conn
Male/FemaleFemale
Electrical connection sizeNPSM 1/2 - 14
Electrical connection standardANSI/ASME B1.20.1
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EU RoHS complianceYes
Max. sensor temperature [°C]120 °C
Max. sensor temperature [°F]248 °F
Parts includedScrews
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Sensor size (Ø x L) [in]1/10 x 19 5/8 in
Sensor size (Ø x L) [mm]2.5 x 500 mm
Sensor typeCapillary tube sensor
Temperature range [°C] [max]15 °C
Temperature range [°C] [min]-30 °C
Temperature range [°F] [max]60 °F
Temperature range [°F] [min]-20 °F
UL approval file nameE31024
UL markYes

Properties

Materialcapillary (contact) sensor with steel housing
Temperature range-40 to +65 °C
IP ratingIP30
MOQ1

Compatibility

KP61 temperature switch for HVAC-R temperature regulation and limit/frost/overheat protection. Contact wired NO or NC. Verify regulating range (-30 to 15 °C) and differential against the set point before ordering.

Standards

Approvals

Attached Documents