Danfoss KP61 thermostat, code 060L110566. Sensor (regulating) range -30 to 15 °C (-22 to 59 °F) via remote air coil 9.5 x 70 mm with 2000 mm capillary tube. Differential 2 K (max range setting); 6 K (min range setting); manual (minimum) reset; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 120 °C. Carries marine type approval (DNV/BV/GL/LR/RINA/RMRS). For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702428014526.
| Type | KP61 thermostat Code number: 060L110566 Sensor (regulating) range: -30 to 15 °C (-22 to 59 °F) Differential: 2 K (max range setting); 6 K (min range setting) Reset: Manual (minimum) reset Contact system: SPDT (single-pole double-throw) Contact rating: AC15 10 A 400 V; AC1 16 A 400 V; AC3 16 A 400 V; DC13 12 W 220 V; LR 112 A 400 V Sensor: remote air coil 9.5 x 70 mm Capillary tube length: 2000 mm Maximum sensor temperature: 120 °C Enclosure: IP30 Ambient temperature: -40 to +65 °C (80 °C for max 120 min) Electrical connection: rubber cable gland 6-14 mm Approvals: CE, EAC, CCC, UL, CSA, DNV, BV, GL, LR, RINA, RMRS, LVD |
| CMIM EAN | 5702428014526 Net weight: 0.36 Kilogram Product group: Switches and thermostats Amb |
| Temp | |
| Note | 80 °C/176 °F for max 120 min Ambient temperature range [°C] [max]: 65 °C Ambient temperature range [°C] [min]: -40 °C Ambient temperature range [°F] [max]: 150 °F Ambient temperature range [°F] [min]: -40 °F Approval: BV Cap. tube length fraction [in]: 78 3/4 in Capillary tube length [mm]: 2000 mm CE mark: Yes Charge type: Vapour China RoHS compliance: Yes Contact function: SPDT Diff. @ Max. range setting [K]: 2 K Diff. @ Max. range setting[°C]: 2 °C Diff. @ Min. range setting [K]: 6 K Diff. @ Min. range setting[°C]: 6 °C Differential type: Fixed Electrical connection size: 6-14 mm Electrical spec. standard: EN 60947-5 EN 60947 electrical properties: Insulation: 400V EN 60947 wiring properties: Flex, ferrules: 0.5-1.5 mm2 Enclosure rating IP: IP30 Enclosure rating Nema (~): 1 EU RoHS compliance: Yes Max. sensor temperature [°C]: 120 °C Max. sensor temperature [°F]: 248 °F REACH Candidate List substances: Lead (CAS no. 7439-92-1) Reset function: Manual Min Sensor size (Ø x L) [in]: 3/8 x 2 3/4 in Sensor size (Ø x L) [mm]: 9.5 x 70 mm Sensor type: Remote air coil Temperature range [°C] [max]: 15 °C Temperature range [°C] [min]: -30 °C Temperature range [°F] [max]: 59 °F Temperature range [°F] [min]: -22 °F UL approval file name: E31024 UL mark: Yes |
| Material | Remote air coil with steel housing |
| Temperature range | -40 to +65 °C (80 °C for max 120 min) |
| IP rating | IP30 |
| MOQ | 1 |
KP61 temperature switch for HVAC-R temperature regulation and frost/overheat protection. SPDT contact wired NO or NC. Verify regulating range (-30 to 15 °C) and differential against the set point before ordering.