cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KP61 thermostat, -30 to 15 °C, automatic reset, SPDT, capillary sensor 2.5 x 500 mm

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L110166  ·  HS 9032.10
Danfoss KP61 thermostat, -30 to 15 °C, automatic reset, SPDT, capillary sensor 2.5 x 500 mm

Danfoss KP61 thermostat (code 060L110166). Sensor (regulating) range -30 to 15 °C with a capillary tube sensor 2.5 x 500 mm (Ø x L) and 5000 mm capillary tube. Adjustable differential 1.5 to 7 K at the maximum range setting (5.5 to 23 K at the minimum range setting); automatic reset; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min). Maximum sensor temperature 120 °C. For temperature monitoring and control of non-aggressive media.

Technical Specifications

TypeKP61 thermostat Code number: 060L110166 Sensor (regulating) range: -30 to 15 °C (-22 to 59 °F) Differential: 1.5 to 7 K (max range setting); 5.5 to 23 K (min range setting), adjustable Reset: Automatic Contact system: SPDT (single-pole double-throw) Sensor: capillary tube sensor 2.5 x 500 mm (Ø x L) Capillary tube length: 5000 mm Maximum sensor temperature: 120 °C Enclosure: IP30 Ambient temperature: -40 to +65 °C (80 °C for max 120 min) Electrical connection: rubber cable gland 6-14 mm Approvals: CE, EAC, CCC, UL (UL873), CSA (C22.2), DNV, BV, GL, LR, RINA, RMRS, LVD
CMIM Product groupSwitches and thermostats Max. sensor temperature: 120 °C Temperature range: -30 °C to 15 °C UL approval file name: E31024 UL mark: Yes CE mark: Yes REACH candidate-list substances: Lead (CAS no. 7439-92-1); Cadmium oxide (CAS no.1306-19-0) Net weight: 0.47 kg EAN: 5702428516884 Amb
Temp
Note80 °C/176 °F for max 120 min Cap. tube length fraction: 196 7/8 in Charge type: Vapour Contact function: SPDT Contact rating: AC15=10 A, 400 V; AC1=16 A, 400 V; AC3=16 A, 400 V; DC13=12 W, 220 V; LR=112 A, 400 V Diff. @ Max. range setting: 1.5 K to 7.0 K, 1.5 °C to 7.0 °C Diff. @ Min. range setting: 5.5 K to 23.0 K, 5.5 °C to 23.0 °C Differential type: Adjustable Electrical connection size: 6-14 mm Electrical spec. standard: EN 60947-5 EN 60947 electrical properties: Insulation: 400V; Pollution degree: 3; Rated impulse voltage: 4 kV; Short circuit prot, fuse: 16A EN 60947 wiring properties: Flex, ferrules: 0.5-1.5 mm2; Flex, no ferrules: 0.7-2.5 mm2; Solid/stranded: 0.75-2.5 mm2 Enclosure rating IP: IP30 Enclosure rating Nema (~): 1 Reset function: Auto Sensor size (Ø x L): 2.5 x 500 mm Sensor type: Capillary tube sensor EU RoHS compliance: Yes

Properties

MaterialCapillary tube sensor with steel housing
Temperature range-40 to +65 °C (80 °C for max 120 min)
IP ratingIP30
MOQ1

Compatibility

Capillary-sensor cooling thermostat for temperature monitoring/control. SPDT contact wired NO or NC. Verify regulating range and differential against the set point before ordering.

Standards

Approvals

Attached Documents