cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss ICLX 32 two-step solenoid valve function module (top assembly) (code 027H3204)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
027H3204  ·  HS 8481.80
Danfoss ICLX 32 two-step solenoid valve function module (top assembly) (code 027H3204)

Danfoss ICLX 32 two-step (pilot-operated) solenoid valve function module / top assembly (code 027H3204), steel, for the ICLX 32 / ICV 32 Flexline valve. Kv 22 m3/h, maximum working pressure 65 bar; media temperature -60 to +120 C. The function module is the complete operating top assembly that mounts onto an ICV PM valve housing to build a two-step ICLX 32 valve; it does not include the valve body. Two-step opening for high differential-pressure duties such as hot-gas defrost in industrial refrigeration; coils ordered separately. Suitable for a broad range of refrigerants including R717 (ammonia) and R744 (CO2).

Technical Specifications

TypeICLX 32 two-step solenoid valve function module (top assembly)
Code number027H3204
Fits valveICLX 32 / ICV 32 (with top assembly)
Nominal size32 mm (1 1/4 in)
Kv value22 m3/h
Body materialSteel
Valve operationSolenoid operated, two-step (pilot-operated)
Functiontop assembly / function module (mounts onto an ICV PM valve housing; valve body ordered separately)
Coilsordered separately (not included)
Maximum working pressure65 bar (943 psig)
Media temperature range-60 to +120 C (-76 to +248 F)
Net weight2.764 kg; gross weight: 5.906 kg
RefrigerantsR717 (ammonia), R744 (CO2), R134a, R404A, R407C, R410A, R290 and others
ApprovalsEAC, TUV, UL
EU RoHS / China RoHScompliant
EAN5702428483155
Product groupPress. and temp. regul. valves
Actuator system2 EVM pilot sol valve module
China RoHS complianceYes with exemptions
China RoHS exemption clause7.1
Cv value [gal/min]25.5 gal/min
DescriptionFunction module
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(a)
Ext pilot pressure connectionWeld nipple (P2 Port)
Kv value [m³/h]22 m³/h
Manual operation optionManual open spindle
Opening configuration1-step (optional setting)
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Step 1 opening degree (~) [%]10 %
Step 2 initializationDelta p < 1.25 bar (18 psig)
Used for productICV 32
Used for product commentsWith top assembly

Properties

MaterialSteel
Pressure rating65 bar
Temperature range-60 to +120 C
MOQ1

Compatibility

Two-step solenoid valve function module (top assembly) for the ICLX 32 / ICV 32 Flexline valve, for high differential-pressure duties (e.g. hot-gas defrost) in industrial refrigeration. Kv 22 m3/h, 65 bar working pressure. Mounts onto an ICV 32 PM valve housing (valve body ordered separately); coils ordered separately. Verify the housing, refrigerant and required Kv against your duty before ordering.

Standards

Approvals

Attached Documents