Danfoss HFI 060 F high pressure float valve (liquid level regulating valve), 150 mm (6 in) flange inlet (DIN 2635/2512-F EN 1092-1 EN 10220), 50 mm (2 in) butt weld outlet, 60 mm nozzle, 1200 kW R717 rated capacity, 25 bar MWP with two external connections for drainage and pressure equalization (code 148G3763)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
148G3763  ·  HS 8481.80
Danfoss HFI 060 F high pressure float valve (liquid level regulating valve), 150 mm (6 in) flange inlet (DIN 2635/2512-F EN 1092-1 EN 10220), 50 mm (2 in) butt weld outlet, 60 mm nozzle, 1200 kW R717 rated capacity, 25 bar MWP with two external connections for drainage and pressure equalization (code 148G3763)

Danfoss HFI 060 F high pressure float valve, code 148G3763, a liquid level regulating (float expansion) valve for industrial refrigeration. HFI is a high-pressure float valve with an internal liquid measuring device; it is designed for direct flange mounting or welding onto plate-heat-exchanger type condensers, and can also be mounted directly on vessels. The valve is direct acting, so no differential pressure is required to activate it: the internal float senses the condensed liquid level and meters high-pressure liquid refrigerant on to the low-pressure side, maintaining the correct liquid level in the high-pressure receiver/condenser. It is equipped with a purge valve for venting non-condensable gases (e.g. air) from the top of the valve housing, which also assists servicing. Inlet connection 150 mm (6 in) flange inlet (DIN 2635/2512-F EN 1092-1 EN 10220); outlet 50 mm (2 in) butt weld; nozzle (orifice) 60 mm. Rated capacity 1200 kW (341 TR) on R717 (ammonia) at Temp. -10 - 35 °C; valve constant 50.36. This version has two external connections on the housing for drainage and pressure equalization. Housing (shell and flange) is special steel approved for low-temperature application. Suitable for R717 (ammonia), HCFC and HFC refrigerants with a liquid density of 500-700 kg/m³. Maximum working pressure 25 bar (363 psig); media temperature range -50 °C to +80 °C (-58 °F to +176 °F). PED category III. CE marked; EAC (EAEU) certified.

Technical Specifications

TypeDanfoss HFI 060 F high pressure float valve (liquid level regulating valve)
Code number148G3763
SeriesHFI (high pressure float valve with internal liquid measuring device)
Functionfloat-operated high-pressure liquid level regulation / float expansion (direct acting; maintains liquid level in high-pressure receiver / condenser)
Nozzle (orifice) size60 mm
Inlet connection typeFlange
Inlet connection size150 mm (6 in)
Outlet connection typeButt weld
Outlet connection size50 mm (2 in)
Connection standardDIN 2635/2512-F EN 1092-1 EN 10220
Side branch 1 connection3/8 in
Side branch 2 connection1/2 in
External connectionstwo, for drainage and pressure equalization
Purge valveyes (for venting non-condensable gases)
Rated capacity (R717)1200 kW (341 TR)
Rated capacity conditionsR717: Temp. -10 - 35 °C
Valve constant50.36
Maximum working pressure25 bar (363 psig)
Media temperature range-50 °C to +80 °C (-58 °F to +176 °F)
RefrigerantsR134a R22 R401A R402A R404A R407A R407B R407C R407F R409A R410A R421A R502 R717 R507A
Suitable refrigerant liquid density500-700 kg/m³
Housing materialspecial steel approved for low-temperature application
PED categoryIII
ApprovalsCE marked; EAC (EAEU) certified
Net weight41.1 Kilogram
Gross weight49.4 Kilogram
EAN5702428413305

Properties

MaterialLow-temperature steel
Pressure rating25 bar
Temperature range-50 °C to +80 °C
Primary standardDIN 2635/2512-F EN 1092-1 EN 10220
Standard size150 mm
MOQ1

Compatibility

Danfoss HFI 060 F is selected by refrigeration capacity and condenser/receiver connection: match the nozzle (orifice) size (60 mm), inlet connection type and size (150 mm/6 in flange), and connection standard (DIN 2635/2512-F EN 1092-1 EN 10220). Type suffix F = flange inlet; suffix FD / "two external connections" version adds housing connections for drainage and pressure equalization. Capacity 1200 kW is rated on R717 (ammonia). Float valve inserts, purge valves and seal/gasket kits are available separately as HFI spare parts.

Approvals