Danfoss HFI 050 high pressure float valve (liquid level regulating valve), 150 mm (6 in) butt weld inlet EN 10220, 50 mm (2 in) butt weld outlet, 50 mm nozzle, 800 kW R717 rated capacity, 25 bar MWP (code 148G3095)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
148G3095  ·  HS 8481.80
Danfoss HFI 050 high pressure float valve (liquid level regulating valve), 150 mm (6 in) butt weld inlet EN 10220, 50 mm (2 in) butt weld outlet, 50 mm nozzle, 800 kW R717 rated capacity, 25 bar MWP (code 148G3095)

Danfoss HFI 050 high pressure float valve, code 148G3095, a liquid level regulating (float expansion) valve for industrial refrigeration. HFI is a high-pressure float valve with an internal liquid measuring device; it is designed for direct flange mounting or welding onto plate-heat-exchanger type condensers, and can also be mounted directly on vessels. The valve is direct acting, so no differential pressure is required to activate it: the internal float senses the condensed liquid level and meters high-pressure liquid refrigerant on to the low-pressure side, maintaining the correct liquid level in the high-pressure receiver/condenser. It is equipped with a purge valve for venting non-condensable gases (e.g. air) from the top of the valve housing, which also assists servicing. Inlet connection 150 mm (6 in) butt weld inlet EN 10220; outlet 50 mm (2 in) butt weld; nozzle (orifice) 50 mm. Rated capacity 800 kW (227 TR) on R717 (ammonia) at Temp. -10 - 35 °C; valve constant 33.58. Housing (shell and flange) is special steel approved for low-temperature application. Suitable for R717 (ammonia), HCFC and HFC refrigerants with a liquid density of 500-700 kg/m³. Maximum working pressure 25 bar (363 psig); media temperature range -50 °C to +80 °C (-58 °F to +176 °F). PED category III. CE marked; EAC (EAEU) certified.

Technical Specifications

TypeDanfoss HFI 050 high pressure float valve (liquid level regulating valve)
Code number148G3095
SeriesHFI (high pressure float valve with internal liquid measuring device)
Functionfloat-operated high-pressure liquid level regulation / float expansion (direct acting; maintains liquid level in high-pressure receiver / condenser)
Nozzle (orifice) size50 mm
Inlet connection typeButt weld
Inlet connection size150 mm (6 in)
Outlet connection typeButt weld
Outlet connection size50 mm (2 in)
Connection standardEN 10220
Purge valveyes (for venting non-condensable gases)
Rated capacity (R717)800 kW (227 TR)
Rated capacity conditionsR717: Temp. -10 - 35 °C
Valve constant33.58
Maximum working pressure25 bar (363 psig)
Media temperature range-50 °C to +80 °C (-58 °F to +176 °F)
RefrigerantsR134a R22 R401A R402A R404A R407A R407B R407C R407F R409A R410A R421A R502 R717 R507A
Suitable refrigerant liquid density500-700 kg/m³
Housing materialspecial steel approved for low-temperature application
PED categoryIII
ApprovalsCE marked; EAC (EAEU) certified
Net weight39.49 Kilogram
Gross weight47.49 Kilogram
EAN5702428343961

Properties

MaterialLow-temperature steel
Pressure rating25 bar
Temperature range-50 °C to +80 °C
Primary standardEN 10220
Standard size150 mm
MOQ1

Compatibility

Danfoss HFI 050 is selected by refrigeration capacity and condenser/receiver connection: match the nozzle (orifice) size (50 mm), inlet connection type and size (150 mm/6 in butt weld), and connection standard (EN 10220). Type suffix F = flange inlet; suffix FD / "two external connections" version adds housing connections for drainage and pressure equalization. Capacity 800 kW is rated on R717 (ammonia). Float valve inserts, purge valves and seal/gasket kits are available separately as HFI spare parts.