Danfoss GD Basic+ fixed gas detection unit, code 148H6009, a factory-calibrated wall-mount detector for ammonia (R717) in refrigeration machinery rooms, cold stores and process plant. Electrochemical sensing element with a 0–300 ppm measuring range and two-level alarm relays (pre-alarm 25 ppm, main alarm 150 ppm). On-board buzzer and light for local annunciation. Supplied as a complete unit with mounting kit, cable gland and a factory calibration certificate. Supply 19–29 V AC/DC. Integrates with Danfoss AK-SM system managers and standard alarm panels. HS 9027.10. OEM P/N 148H6009.
| Type | Gas detection unit — GD Basic+ |
| Code number | 148H6009 |
| Detected gas | ammonia (R717) |
| Sensor technology | electrochemical |
| Measuring range | 0–300 ppm |
| Pre-alarm (low) set point | 25 ppm |
| Main alarm (high) set point | 150 ppm |
| Local annunciation | buzzer and light |
| Supply voltage | 19–29 V AC/DC |
| Operating temperature | -40 to +50 °C |
| Enclosure | wall-mount, includes mounting kit and cable gland |
| Supplied with | factory calibration certificate |
| Approvals | EU RoHS; China RoHS |
| EAN | 5714279919936 |
| Net weight | 0.282 Kilogram |
| Product group | Sensors |
| Alarmlimits high [ppm] sensor1 | 150 ppm |
| Alarmlimits low [ppm] sensor1 | 25 ppm |
| China RoHS compliance | Yes |
| Division | 40 |
| Equipment | Buzzer & Light |
| EU RoHS compliance | Yes |
| Frequency [Hz] | 50/60 Hz |
| Gas detecting sensor version | Basic + |
| Parts included | Cable gland |
| PFAS content [Yes/No] | No |
| Power consumption [A] | 0.25 A |
| REACH Candidate List substances | No |
| Refrig. range [ppm] sensor1 [max] | 300 ppm |
| Refrig. range [ppm] sensor1 [min] | 0 ppm |
| Refrigerants | R717 |
| Relative humidity (RH) [%] [max] | 90 % |
| Relative humidity (RH) [%] [min] | 15 % |
| Response delay [s] | 0 s |
| Sensor 1 type | Electrochemical |
| Supply voltage [V] AC [max] | 29 V |
| Supply voltage [V] AC [min] | 19 V |
| Supply voltage [V] DC [max] | 29 V |
| Supply voltage [V] DC [min] | 19 V |
| Temperature range [°C] [max] | 50 °C |
| Temperature range [°C] [min] | -40 °C |
| Temperature range [°F] [max] | 122 °F |
| Temperature range [°F] [min] | -40 °F |
| Temperature range | -40 to +50 °C |
| MOQ | 1 |
Confirm the target gas (ammonia (R717)), detection range (0–300 ppm) and supply voltage (19–29 V AC/DC) match the installation before ordering; sensor element is gas-specific and factory-calibrated. Alarm set points 25/150 ppm are the Danfoss defaults; display-equipped GD versions allow the thresholds to be reconfigured.