Danfoss GD replacement sensor cartridge, code 148H6201, a field-replaceable electrochemical sensing head for Danfoss GD gas detection units monitoring ammonia (R717). Factory-calibrated 0–300 ppm cartridge with a polycarbonate housing; alarm set points 25/150 ppm. Plugs into the installed GD unit base so a sensor at end of life is renewed without replacing the whole detector or rewiring. Ships with a calibration certificate. Compatible across the GD unit versions. Operating temperature -30 to +50 °C. CE and UL marked. HS 9027.90. OEM P/N 148H6201.
| Type | GD replacement sensor cartridge |
| Code number | 148H6201 |
| Detected gas | ammonia (R717) |
| Sensor technology | electrochemical |
| Measuring range | 0–300 ppm |
| Pre-alarm (low) set point | 25 ppm |
| Main alarm (high) set point | 150 ppm |
| Cartridge housing material | polycarbonate |
| Operating temperature | -30 to +50 °C |
| Supplied with | calibration certificate |
| Fitment | field-replaceable head for Danfoss GD gas detection units |
| Approvals | CE; UL; EU RoHS; China RoHS |
| EAN | 5714279924657 |
| Net weight | 0.022 Kilogram |
| Product group | Sensors |
| Alarm limits high [ppm] | 150 ppm |
| Alarm limits low [ppm] | 25 ppm |
| Approval | CE |
| CE mark | Yes |
| China RoHS compliance | Yes |
| Division | 40 |
| EU RoHS compliance | Yes |
| Gas detecting sensor version | Basic |
| Parts included | Sensor replacement |
| PFAS content [Yes/No] | No |
| REACH Candidate List substances | No |
| Refrigerants | R717 |
| Refrigerants range [ppm] [max] | 300 ppm |
| Refrigerants range [ppm] [min] | 0 ppm |
| Sensor cartridge material | Polycarbonate |
| Sensor type | Electrochemical |
| Temperature range [°C] [max] | 50 °C |
| Temperature range [°C] [min] | -30 °C |
| Temperature range [°F] [max] | 122 °F |
| Temperature range [°F] [min] | -22 °F |
| UL mark | Yes |
| Temperature range | -30 to +50 °C |
| MOQ | 1 |
Match the cartridge gas (ammonia (R717)) and range (0–300 ppm) to the host GD unit — the sensor element is gas- and range-specific. Recalibrate after fitting per the Danfoss GD service instruction.