Danfoss GBC 28s shut-off (stop) ball valve, code 009L7100: a straightway two-way brass ball valve for commercial air-conditioning and refrigeration lines. Bi-directional flow, solder, ODM, 1 1/8 in, inlet and outlet. Integral access (charging) port. Maximum working pressure 45 bar (650 psig); media temperature -40 °C to 100 °C. Brass body with copper tube connections and a wire-seal cap. Approved C UL US Listed, CE, EAC, EURO-TYSK. Technical data quoted verbatim from store.danfoss.com (code 009L7100).
| Brand | Danfoss |
| Part number | 009L7100 |
| Model | GBC 28s shut-off (stop) ball valve, with access (charging) port |
| Category | HVAC & Refrigeration — Ball Valves |
| Direction | Straightway |
| Flow | Bi-directional (valve orientation is unimportant) |
| Connection | Solder, ODM, 1 1/8 in, inlet and outlet |
| Access port | Yes |
| Max working pressure (PS/MWP) | 45 bar (650 psig) |
| Media temperature range | -40 °C to 100 °C (-40 °F to 212 °F) |
| Max media temperature, oil-free | 80 °C |
| Kv | 62.25 m³/h |
| Cv | 71.96 gal/min |
| Net weight | 0.893 kg |
| Gross weight | 1.143 kg |
| Body material | Brass; connection material: copper |
| Equipment | Cap w. wire seal |
| Parts included | Schrader valve |
| Panel mounting option | M4 × 0.7 (2 PC) |
| Fluid group | 1 2 |
| PED category | Art. 4, par. 3 |
| Approvals | C UL US Listed, CE, EAC, EURO-TYSK |
| Packing | 5 pc per multi-pack |
| EAN | 5702424494421 |
| Refrigerant compatibility | R1234yf R1234ze(E) R134a R22/R407C R290 R32 R404A/R507A R407A R407F R407H R410A R448A R449A R449B R450A R452A R452B R454A R454B R454C R455A R463A R513A R515B R516A R600 R600a R1270 |
| Oil-free refrigerants | R1234ze(E) R134a R513A R515B R516A |
| Material | Brass body; copper tube connections |
| Pressure rating | 45 bar (650 psig) max working pressure |
| Temperature range | -40 °C to 100 °C |
| Primary standard | EN 12284 |
| Standard size | 1 1/8 in |
| MOQ | 1 |
Danfoss GBC 28s fits 1 1/8 in ODM solder (copper) connections. Verify the tube dimension (inch copper, ANSI B16.22), the connection form (ODF cup / ODM spigot) and whether an access port is required before ordering.