Danfoss VLT Automation Drive FC-302 — 90 kW, 380 - 480 VAC, IP54. Reference part number 134F0299.
| Type code | FC-302N90KT5E54H4XGCXXXSXXXXAXBXCXXXXDX |
| Code number | 134F0299 |
| Enclosure rating | IP54 |
| Series | VLT Automation Drive FC-302 |
| Supply voltage | 380–480 V AC |
| Power rating | 90 kW |
| IP rating | IP54 |
| Product Group | FC- |
| Phase | T |
| Mains Voltage | 5 |
| Enclosure | E54 |
| RFI Filter | H4 |
| Brake - Safe Stop | X |
| LCP | G |
| Coating PCB | C |
| Mains Option | X |
| Adaptation A | X |
| Adaptation B | X |
| Software Release | SXXX |
| Software Language Pack | X |
| A Option | AX |
| B Option | BX |
| C0 Option MCO | CX |
| C1 Option | X |
| C Option Software | XX |
| D Option | DX |
| Frame Size | D1H |
| Product Catalog | GLBL |
| Power 150% (HO) [KW] | 90 |
| Power 110% (NO) [KW] | 110 |
| Power Loss HO [W] | 2031 |
| Power Loss NO [W] | 2261 |
| kVA | 123 |
| Continuous Current (HO) [A] | 177 |
| Intermittent Current (HO) [A] | 266 |
| Continuous Current (NO) [A] | 190 |
| Intermittent Current (NO) [A] | 233 |
| Height [mm] | 901,0 |
| Width w/ no C options [mm] | 325,0 |
| Depth [mm] | 378,0 |
| Depth with Option A/B [mm] | 378,0 |
| ECCN EU | Y901 |
| ECCN US | 3A999.a |
| Product View (Switch) | GLBL |
| MOQ | 1 |