Danfoss EMP 2 Pressure Transmitter - 1/2", 0-6bar

Danfoss · Sensors & Instrumentation · Pressure Transmitters · Denmark · danfoss.com
Part Number
084G2108  ·  HS 9026.20
Danfoss EMP 2 Pressure Transmitter - 1/2", 0-6bar

Danfoss EMP 2 Pressure Transmitter. Push buttons (Plumbing / Heat / Valves for heating and cooling systems). Principal data: connection 1/2", setting range 0-6 bar. Supplied under manufacturer part number 084G2108, EAN 5702423016389, HS code 9026.20, country of origin China.

Technical Specifications

Product typePush buttons
Product groupHeat
Connection1/2"
Setting range0-6 bar
TypeEMP 2
REACH SVHC substance above 0.1%Lead
Carbon footprint (EPD)7.3634 kg CO2e per pcs
Country of originChina
Customs tariff code (EU CN)90262020
HS code9026.20
Manufacturer part number084G2108
VVS number475171108
EAN5702423016389
Net weight0.98 Kilogram
+ supplyP
- commonN
Accuracy, max. [±FS%]1 %
Accuracy, typical [±FS%]0.5 %
ApprovalABS
CE markYes
China RoHS complianceOut of scope
Compensated temp. range [°C] [max]70 °C
Compensated temp. range [°C] [min]0 °C
Compensated temp. range [°F] [max]158 °F
Compensated temp. range [°F] [min]32 °F
Electrical connectionTerminal block
Electrical connection sizePg 13.5
Enclosure rating IPIP65
EU RoHS complianceYes with exemptions
EU RoHS exemption clause7(c)-I
Flush diaphragmNo
High Clipping Level22.4
International Article Number5702423016389
Intrinsically safeNo
Low Clipping level3.6
Medium temperature range [°C] [max]70 °C
Medium temperature range [°C] [min]-10 °C
Medium temperature range [°F] [max]158 °F
Medium temperature range [°F] [min]14 °F
Non-linearity BFSL [±FS%]0.3 %
Output signalCurrent
Output signal [mA] [max]20 mA
Output signal [mA] [min]4 mA
Overload pressure max. [bar]60 bar
Pressure connection notesEXT. G1/4 INT
Pressure connection size1/2
Pressure connection standardEN 228-1
Pressure connection typeG
Pressure Male/FemaleMale/Female
Pressure range [bar] [max]6 bar
Pressure range [bar] [min]0 bar
Pressure range [psi] [max]87 psi
Pressure range [psi] [min]0 psi
Pressure referenceGauge (relative)
Pulse-snubberYes
REACH Candidate Strip substancesLead (CAS no. 7439-92-1)
Response time max. [ms]4 ms
Specification keyEMP 2-1811-F6CD24-2
Supply voltage [V] DC [max]32 V
Supply voltage [V] DC [min]12 V
UL markYes

Properties

MOQ1

Cross-References

Attached Documents