Danfoss CHV-X 32 angleway check valve, 32 mm (1 1/4 in) butt weld EN 10220, 52 bar, steel (code 148B5536)

Danfoss · HVAC & Refrigeration · Check Valves · Denmark · danfoss.com
Part Number
148B5536  ·  HS 8481.30
Danfoss CHV-X 32 angleway check valve, 32 mm (1 1/4 in) butt weld EN 10220, 52 bar, steel (code 148B5536)

Danfoss CHV-X 32 check (non-return) valve for the SVL Flexline industrial-refrigeration range, code 148B5536. The CHV-X permits refrigerant flow in one direction only and closes to prevent back-flow toward pumps, compressors and vessels. The cold-resistant steel housing carries a spring-loaded, guided cone with a V-port profile that throttles below roughly 25% lift to suppress valve chatter and noise. This SKU is the angleway body with 32 mm (1 1/4 in) butt-weld connections to EN 10220. Flow coefficient Kv 30 m3/h (Cv 34.8 gal/min); minimum opening differential pressure 0.04 bar (0.62 psi); flow direction marked by an embossed 1-way arrow. Maximum working pressure 52 bar (754 psig); media temperature range -60 to 150 C (-76 to 302 F). For HCFC, non-flammable HFC, R717 (ammonia) and R744 (CO2) systems. Built on the SVL Flexline modular platform and serviceable with SVL Flexline spare parts.

Technical Specifications

TypeCHV-X 32 (SVL Flexline check valve) Code number: 148B5536 Series: CHV-X (SVL Flexline) Function: Check (non-return) valve Nominal size: 32 mm (1 1/4 in) Flow direction: Angleway Connection: Butt weld (EN 10220) Housing material: Steel (cold-resistant) Kv value: 30 m3/h (Cv 34.8 gal/min) minimum opening differential pressure: 0.04 bar (0.62 psi) Flow direction indicator: Embossed 1-way arrow Maximum working pressure: 52 bar (754 psig) Media temperature range: -60 to 150 C (-76 to 302 F) Applicable media: HCFC, HFC, R717 (ammonia)
R744 (CO2) Fluid groups1, 2 Conformity assessment: PED Category II Approvals: CE
PED Category II ComplianceEU RoHS
China RoHS Net weight2.572 kg EAN: 5702428477222

Properties

MaterialSteel
Pressure rating52 bar
Temperature range-60 to 150 C
Standard size32 mm
MOQ1

Compatibility

Danfoss SVL Flexline CHV-X check valve. Select by nominal size (32 mm / 1 1/4 in) and connection standard (EN 10220 butt weld). EN 10220 (DIN) and ASME B 36.10M weld-end preparations are not interchangeable — confirm the mating pipe schedule before ordering. The CHV-X is check-only; where an integral hand shut-off is also required, use the SCA-X stop/check valve of the same size. Mount with the embossed arrow in the direction of intended flow.