cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-09
sales@cballast.com
cballast.com

Danfoss CHV-X 125 function module (Top Complete), fits SVL Flexline CHV-X 125 check valve, 65 bar (code 148B5782)

Danfoss · HVAC & Refrigeration · Check Valves · Denmark · danfoss.com
Part Number
148B5782  ·  HS 8481.90
Danfoss CHV-X 125 function module (Top Complete), fits SVL Flexline CHV-X 125 check valve, 65 bar (code 148B5782)

Danfoss CHV-X 125 function module (also called Top Complete) for the SVL Flexline modular industrial-refrigeration platform, store code 148B5782. The function module is the complete field-serviceable non-return (check) operating top part — supplied as the top part with one gasket and the mounting bolts — that fits the matching CHV-X 125 check valve housing. It gives the spring-loaded non-return (check) function that allows flow one way and closes on reverse flow, protecting compressors and pumps against back-flow. It is the repair/replacement assembly, not a complete valve and not a loose gasket, so the function can be renewed without cutting the housing out of the line. For R717 (ammonia), R744 (CO2) and fluorinated refrigerants and their oils. Maximum working pressure 65 bar g (943 psig); media temperature -60 to 150 C (-76 to 302 F). net weight 9.819 kg, gross weight 10.73 kg. Specifications per Danfoss store code 148B5782.

Technical Specifications

TypeCHV-X 125 function module (Top Complete)
Code number148B5782
FitsSVL Flexline CHV-X 125 check valve
Functionnon-return (check) operating top part
Parts includedtop part, 1 gasket, bolts
Maximum working pressure65 bar g (943 psig)
Media temperature range-60 to 150 C (-76 to 302 F)
Applicable mediaR717 (ammonia), R744 (CO2), HFC/HCFC refrigerants and oils
Weightnet weight 9.819 kg, gross weight 10.73 kg
ApprovalsCE
EAN5702428500531
BrandSVL Flexline
Product groupCheck valves
Type designationTop Complete
Max. working pressure65.0 bar
Temperature range-60 °C to 150 °C
RefrigerantsR1234yf; R1234ze(E); R125; R134a; R152a; R170; R22; R227ea; R236fa; R245fa; R290; R32; R401A; R402A; R404A; R407A; R407B; R407C; R407F; R407H; R409A; R410A; R413A; R417A; R421A; R422A; R422B; R422D; R438A; R442A; R444B; R447A; R447B; R448A; R449A; R449B; R450A; R452A; R452B; R452C; R454A; R454B; R454C; R455A; R463A; R502; R507A; R512A; R513A; R513B; R515A; R515B; R516A; R600; R600a; R717; R744
REACH candidate-list substancesNo
EU RoHS complianceYes
Net weight9.819 Kilogram
ApprovalCE
China RoHS complianceYes
Max. Working Pressure [bar]65 bar
Max. Working Pressure [psig]943 psig
Temperature range [°C] [max]150 °C
Temperature range [°C] [min]-60 °C
Temperature range [°F] [max]302 °F
Temperature range [°F] [min]-76 °F
Used for productCHV-X 125

Properties

MaterialSteel
Pressure rating65 bar
Temperature range-60 to 150 C
MOQ1

Compatibility

Danfoss SVL Flexline CHV-X 125 function module (Top Complete). Mounts on the matching CHV-X 125 check valve housing of the same nominal-size class. Function modules are size-specific — confirm the housing size class (125) before ordering. Shares the SVL Flexline platform with SVA-S/SVA-L shut-off, REG regulating, SCA-X/CHV-X check and FIA strainer components of the same size.

Standards

Approvals

Attached Documents