Danfoss CHV-X 125 function module (also called Top Complete) for the SVL Flexline modular industrial-refrigeration platform, store code 148B5782. The function module is the complete field-serviceable non-return (check) operating top part — supplied as the top part with one gasket and the mounting bolts — that fits the matching CHV-X 125 check valve housing. It gives the spring-loaded non-return (check) function that allows flow one way and closes on reverse flow, protecting compressors and pumps against back-flow. It is the repair/replacement assembly, not a complete valve and not a loose gasket, so the function can be renewed without cutting the housing out of the line. For R717 (ammonia), R744 (CO2) and fluorinated refrigerants and their oils. Maximum working pressure 65 bar g (943 psig); media temperature -60 to 150 C (-76 to 302 F). net weight 9.819 kg, gross weight 10.73 kg. Specifications per Danfoss store code 148B5782.
| Type | CHV-X 125 function module (Top Complete) |
| Code number | 148B5782 |
| Fits | SVL Flexline CHV-X 125 check valve |
| Function | non-return (check) operating top part |
| Parts included | top part, 1 gasket, bolts |
| Maximum working pressure | 65 bar g (943 psig) |
| Media temperature range | -60 to 150 C (-76 to 302 F) |
| Applicable media | R717 (ammonia), R744 (CO2), HFC/HCFC refrigerants and oils |
| Weight | net weight 9.819 kg, gross weight 10.73 kg |
| Approvals | CE |
| EAN | 5702428500531 |
| Brand | SVL Flexline |
| Product group | Check valves |
| Type designation | Top Complete |
| Max. working pressure | 65.0 bar |
| Temperature range | -60 °C to 150 °C |
| Refrigerants | R1234yf; R1234ze(E); R125; R134a; R152a; R170; R22; R227ea; R236fa; R245fa; R290; R32; R401A; R402A; R404A; R407A; R407B; R407C; R407F; R407H; R409A; R410A; R413A; R417A; R421A; R422A; R422B; R422D; R438A; R442A; R444B; R447A; R447B; R448A; R449A; R449B; R450A; R452A; R452B; R452C; R454A; R454B; R454C; R455A; R463A; R502; R507A; R512A; R513A; R513B; R515A; R515B; R516A; R600; R600a; R717; R744 |
| REACH candidate-list substances | No |
| EU RoHS compliance | Yes |
| Net weight | 9.819 Kilogram |
| Approval | CE |
| China RoHS compliance | Yes |
| Max. Working Pressure [bar] | 65 bar |
| Max. Working Pressure [psig] | 943 psig |
| Temperature range [°C] [max] | 150 °C |
| Temperature range [°C] [min] | -60 °C |
| Temperature range [°F] [max] | 302 °F |
| Temperature range [°F] [min] | -76 °F |
| Used for product | CHV-X 125 |
| Material | Steel |
| Pressure rating | 65 bar |
| Temperature range | -60 to 150 C |
| MOQ | 1 |
Danfoss SVL Flexline CHV-X 125 function module (Top Complete). Mounts on the matching CHV-X 125 check valve housing of the same nominal-size class. Function modules are size-specific — confirm the housing size class (125) before ordering. Shares the SVL Flexline platform with SVA-S/SVA-L shut-off, REG regulating, SCA-X/CHV-X check and FIA strainer components of the same size.