Danfoss CCM 20 electric regulating valve, solder ODF 7/8 in / weld 3/4 in (code 027H7179)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
027H7179  ·  HS 8481.80
Image not available for this product

Danfoss CCM 20 electric regulating valve (code 027H7179), a motor-operated modulating valve for capacity, hot-gas and pressure regulation in R134a, R404A, R449A and R744 (CO2) refrigeration systems. Solder ODF 7/8 in / weld 3/4 in connection; Kv 1.85 m3/h, maximum working pressure 90 bar (1305 psig). The CCM actuator (motor) is ordered separately.

Technical Specifications

TypeCCM 20 electric regulating valve
Code number027H7179
Connection typesolder, ODF
Solder connection size7/8 in
Weld connection size3/4 in
Kv value1.85 m3/h
Maximum working pressure90 bar (1305 psig)
Valve operationelectrically (motor) operated
RefrigerantsR134a, R404A, R449A, R744
Net weight2.062 kg; gross weight: 2.693 kg
ApprovalsUL (cURus)
REACH candidate substanceLead (CAS 7439-92-1)
EAN5715162732144
Product groupPress. and temp. regul. valves
Ambient temperature range [°C] [max]60 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]140 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalLLC CDC TYSK
China RoHS complianceYes with exemptions
China RoHS exemption clause7.1
Connection Solder size [in]7/8 in
Connection standardEN10220
Connection Weld size [in]3/4 in
Cv value [gal/min]1.856 gal/min
Diff.press.setting range [bar]50 bar
Diff.press.setting range [psi]725 psi
Enclosure rating IPIP67
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(a)
Kv value [m³/h]1.85 m³/h
Max. Working Pressure [bar]90 bar
Max. Working Pressure [psig]1305 psig
MaxOPD [bar]50 bar
MaxOPD [psig]725 psig
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Temperature range [°C] [max]60 °C
Temperature range [°C] [min]-40 °C
Temperature range [°F] [max]140 °F
Temperature range [°F] [min]-40 °F
UL approved refrigerantsR134a
UL markYes

Properties

Pressure rating90 bar
MOQ1

Compatibility

CCM 20 for capacity/hot-gas control. Confirm Kv (1.85 m3/h) and MWP (90 bar); the CCM actuator (motor) and controller are ordered separately.