Danfoss AVQT flow and temperature controller, PN 25, DN 15, flow range 0.07–2.4 m³/h, Kvs 4 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces (003H6761)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6761  ·  HS 8481.80
Danfoss AVQT flow and temperature controller, PN 25, DN 15, flow range 0.07–2.4 m³/h, Kvs 4 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces (003H6761)

Danfoss AVQT (003H6761) — self-acting flow and temperature controller, PN 25, DN 15, for district heating and cooling systems. The AVQT holds the flow constant and limits it to the set maximum and closes on rising temperature. It accepts an AVT thermostatic actuator, or an STM safety temperature monitor where over-temperature protection is required. It comprises a control valve with adjustable flow restrictor, a connection neck for the thermostatic actuator, and a pressure actuator with one control diaphragm. Flow range 0.07 - 2.4 m³/h; flow-restrictor differential pressure 0.2 bar; Kvs 4 m³/h. Maximum differential-pressure range 20 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.02 % Kvs (IEC 60534). Temperature is set by the separately ordered AVT thermostatic actuator, setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately); the controller is delivered assembled with the impulse tube between valve and actuator, the actuator ordered separately. Combined with AMV(E), AVT or STM actuators the controller is type-tested to EN 14597. Valve body Red bronze CuSn5ZnPb (Rg5); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection External thread G 3/4 A (ISO 228/1), via tailpieces. Mounting version Free. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%), pH 7–10. OEM P/N 003H6761. Technical data quoted verbatim from store.danfoss.com (code 003H6761) and the Danfoss AVQT / AVQMT (PN 25) data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 20 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants. No.

Technical Specifications

Code number003H6761
TypeAVQT
Product groupPressure and flow controllers
FunctionSelf-acting flow and temperature controller (limits max. flow; closes on rising temperature; accepts AVT/STM thermostatic actuator)
Valve sizeDN 15
Pressure classPN 25
ConnectionExternal thread G 3/4 A (ISO 228/1), via tailpieces
Kvs value4 m³/h
Flow rate range0.07 - 2.4 m³/h
Flow restrictor differential pressure (Δpb)0.2 bar
Max. differential pressure range20 bar
Media temperature2 - 150 °C
Temperature setting ranges (AVT actuator, ordered separately)10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately)
Media pH7 - 10
Cavitation factor z≥ 0.6
Seat leakage rate0.02 % Kvs (IEC 60534)
Mounting versionFree
Stem positionNormally open
Stroke5 mm
Type testEN 14597 (controller combined with AMV(E) / AVT / STM actuator)
Permissible mediaDistrict heating/cooling circulation water (Glycolic water up to 30%)
Valve body materialRed bronze CuSn5ZnPb (Rg5)
Valve cone materialDezincing free brass CuZn36Pb2As
Valve seat materialStainless steel, mat. No. 1.4571
Actuator diaphragmEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
China RoHSOut of scope
Net weight3.074 kg
Gross weight3.074 kg
EAN5702421542828

Properties

MaterialValve body Red bronze CuSn5ZnPb (Rg5); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM
Pressure ratingPN 25 (max. differential-pressure range 20 bar)
Temperature range2 to 150 °C (district heating/cooling water)
MOQ1

Compatibility

Danfoss AVQT for DN 15 district-heating/cooling combined flow limiting and temperature control at PN 25. Set the maximum flow within 0.07 - 2.4 m³/h using the adjustable flow restrictor (Kvs 4 m³/h). Fit a Danfoss AVT thermostatic actuator to set the temperature, or an STM safety temperature monitor for over-temperature protection (ordered separately). Temperature setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately). Confirm the connection (External thread G 3/4 A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut or flange set separately. Maximum differential-pressure range 20 bar, media temperature up to 150 °C.