Danfoss AVQT (003H6760) — self-acting flow and temperature controller, PN 25, DN 15, for district heating and cooling systems. The AVQT holds the flow constant and limits it to the set maximum and closes on rising temperature. It accepts an AVT thermostatic actuator, or an STM safety temperature monitor where over-temperature protection is required. It comprises a control valve with adjustable flow restrictor, a connection neck for the thermostatic actuator, and a pressure actuator with one control diaphragm. Flow range 0.07 - 1.6 m³/h; flow-restrictor differential pressure 0.2 bar; Kvs 2.5 m³/h. Maximum differential-pressure range 20 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.02 % Kvs (IEC 60534). Temperature is set by the separately ordered AVT thermostatic actuator, setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately); the controller is delivered assembled with the impulse tube between valve and actuator, the actuator ordered separately. Combined with AMV(E), AVT or STM actuators the controller is type-tested to EN 14597. Valve body Red bronze CuSn5ZnPb (Rg5); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection External thread G 3/4 A (ISO 228/1), via tailpieces. Mounting version Free. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%), pH 7–10. OEM P/N 003H6760. Technical data quoted verbatim from store.danfoss.com (code 003H6760) and the Danfoss AVQT / AVQMT (PN 25) data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 20 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants. No.
| Code number | 003H6760 |
| Type | AVQT |
| Product group | Pressure and flow controllers |
| Function | Self-acting flow and temperature controller (limits max. flow; closes on rising temperature; accepts AVT/STM thermostatic actuator) |
| Valve size | DN 15 |
| Pressure class | PN 25 |
| Connection | External thread G 3/4 A (ISO 228/1), via tailpieces |
| Kvs value | 2.5 m³/h |
| Flow rate range | 0.07 - 1.6 m³/h |
| Flow restrictor differential pressure (Δpb) | 0.2 bar |
| Max. differential pressure range | 20 bar |
| Media temperature | 2 - 150 °C |
| Temperature setting ranges (AVT actuator, ordered separately) | 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately) |
| Media pH | 7 - 10 |
| Cavitation factor z | ≥ 0.6 |
| Seat leakage rate | 0.02 % Kvs (IEC 60534) |
| Mounting version | Free |
| Stem position | Normally open |
| Stroke | 5 mm |
| Type test | EN 14597 (controller combined with AMV(E) / AVT / STM actuator) |
| Permissible media | District heating/cooling circulation water (Glycolic water up to 30%) |
| Valve body material | Red bronze CuSn5ZnPb (Rg5) |
| Valve cone material | Dezincing free brass CuZn36Pb2As |
| Valve seat material | Stainless steel, mat. No. 1.4571 |
| Actuator diaphragm | EPDM |
| EU RoHS compliance | Yes with exemptions (6(c)) |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| China RoHS | Out of scope |
| Net weight | 3.065 kg |
| Gross weight | 3.065 kg |
| EAN | 5702421542811 |
| Material | Valve body Red bronze CuSn5ZnPb (Rg5); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM |
| Pressure rating | PN 25 (max. differential-pressure range 20 bar) |
| Temperature range | 2 to 150 °C (district heating/cooling water) |
| MOQ | 1 |
Danfoss AVQT for DN 15 district-heating/cooling combined flow limiting and temperature control at PN 25. Set the maximum flow within 0.07 - 1.6 m³/h using the adjustable flow restrictor (Kvs 2.5 m³/h). Fit a Danfoss AVT thermostatic actuator to set the temperature, or an STM safety temperature monitor for over-temperature protection (ordered separately). Temperature setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately). Confirm the connection (External thread G 3/4 A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut or flange set separately. Maximum differential-pressure range 20 bar, media temperature up to 150 °C.