cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss AVQMT flow and temperature controller with integrated control valve (PICV), PN 25, DN 50, flow range 0.8–14 m³/h, Kvs 25 m³/h, Flange DN 50 (EN 1092-2) (003H6782)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6782  ·  HS 8481.80
Danfoss AVQMT flow and temperature controller with integrated control valve (PICV), PN 25, DN 50, flow range 0.8–14 m³/h, Kvs 25 m³/h, Flange DN 50 (EN 1092-2) (003H6782)

Danfoss AVQMT (003H6782) — self-acting flow and temperature controller with integrated pressure-independent control valve, PN 25, DN 50, for district heating and cooling systems. The AVQMT holds the flow constant and limits it to the set maximum and closes on rising temperature; the integrated control valve accepts a Danfoss AMV(E) electric actuator (for ECL electronic control) or an AVT/STM thermostatic actuator for combined flow and temperature control. It comprises a control valve with adjustable flow restrictor, a connection neck for the thermostatic actuator, a connection neck for the electric actuator, and a pressure actuator with one control diaphragm. Flow range 0.8 - 14 m³/h; flow-restrictor differential pressure 0.2 bar; Kvs 25 m³/h. Maximum differential-pressure range 16 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.05 % Kvs (IEC 60534). Temperature is set by the separately ordered AVT thermostatic actuator, setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately); the controller is delivered assembled with the impulse tube between valve and actuator, the actuator ordered separately. Combined with AMV(E), AVT or STM actuators the controller is type-tested to EN 14597. Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection Flange DN 50 (EN 1092-2). Mounting version Free. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%), pH 7–10. OEM P/N 003H6782. Technical data quoted verbatim from store.danfoss.com (code 003H6782) and the Danfoss AVQT / AVQMT (PN 25) data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H6782
TypeAVQMT
Product groupPressure and flow controllers
FunctionSelf-acting flow and temperature controller with integrated pressure-independent control valve (limits max. flow; closes on rising temperature; accepts AMV(E) electric or AVT/STM thermostatic actuator)
Valve sizeDN 50
Pressure classPN 25
ConnectionFlange DN 50 (EN 1092-2)
Kvs value25 m³/h
Flow rate range0.8 - 14 m³/h
Flow restrictor differential pressure (Δpb)0.2 bar
Max. differential pressure range16 bar
Media temperature2 - 150 °C
Temperature setting ranges (AVT actuator, ordered separately)10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately)
Media pH7 - 10
Cavitation factor z≥ 0.6
Seat leakage rate0.05 % Kvs (IEC 60534)
Mounting versionFree
Stem positionNormally open
Stroke5 mm
Type testEN 14597 (controller combined with AMV(E) / AVT / STM actuator)
Permissible mediaDistrict heating/cooling circulation water (Glycolic water up to 30%)
Valve body materialDuctile iron EN-GJS-400-18-LT (GGG 40.3)
Valve cone materialDezincing free brass CuZn36Pb2As
Valve seat materialStainless steel, mat. No. 1.4571
Actuator diaphragmEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
China RoHSOut of scope
Net weight14.306 kg
Gross weight14.306 kg
EAN5702421543030

Properties

MaterialValve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM
Pressure ratingPN 25 (max. differential-pressure range 16 bar)
Temperature range2 to 150 °C (district heating/cooling water)
MOQ1

Compatibility

Danfoss AVQMT for DN 50 district-heating/cooling combined flow limiting and temperature control at PN 25. Set the maximum flow within 0.8 - 14 m³/h using the adjustable flow restrictor (Kvs 25 m³/h). The integrated control valve accepts a Danfoss AMV(E) electric actuator (ECL control) or an AVT/STM thermostatic actuator for combined flow/temperature control (ordered separately). Temperature setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately). Confirm the connection (Flange DN 50 (EN 1092-2)) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut or flange set separately. Maximum differential-pressure range 16 bar, media temperature up to 150 °C.

Attached Documents