Danfoss AVPQT (003H6808) — self-acting multi-functional controller combining differential-pressure control, flow limitation and return-temperature limitation, PN 25, DN 20, return-pipe mounting, for district heating and domestic-hot-water substations. The AVPQT combines three self-acting functions in one valve: differential-pressure control, flow (volume) limitation and, via a thermostatic element, temperature limitation of the return. It maintains a constant differential pressure across the integrated flow-limiting valve while the thermostatic actuator throttles on rising return temperature — no auxiliary energy required. kVS 6.3 m³/h; flow-rate range 0.16 – 3.5 m³/h at Δpb 0.2 bar; differential-pressure setting 0.2 – 1 bar; maximum differential pressure 12 bar; medium temperature 2–150 °C; leakage 0.02% of kVS (IEC 534). Valve body red bronze CuSn5ZnPb (Rg5), valve seat stainless steel 1.4571, valve cone dezincing free brass CuZn36Pb2As, control diaphragm EPDM. Connection external thread G 1 A (ISO 228/1). OEM P/N 003H6808, EAN 5702421543290. Technical data quoted verbatim from store.danfoss.com (code 003H6808). differential pressure 12 bar); Temperature range: 2 – 150 °C (medium); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Code number | 003H6808 |
| Type | AVPQT |
| Product group | Pressure and flow controllers (multi-functional) |
| Description | Self-acting combined differential-pressure, flow-limiting and temperature controller, return mounting |
| Valve size | DN 20 |
| Pressure class | PN 25 |
| kVS value | 6.3 m³/h |
| Flow-rate range | 0.16 – 3.5 m³/h |
| Flow restrictor differential pressure (Δpb) | 0.2 bar |
| Connection | external thread G 1 A (ISO 228/1) |
| Differential pressure setting | 0.2 – 1 bar (adjustable) |
| Max. differential pressure | 12 bar |
| Application | District Heating |
| Medium | Circulation water / glycolic water up to 30% (pH 7–10) |
| Medium temperature | 2 – 150 °C |
| Leakage (IEC 534) | 0.02% of kVS |
| Mounting version | Return |
| Stem position | Normally open |
| Valve body | Red bronze CuSn5ZnPb (Rg5) |
| Valve seat | Stainless steel, mat. No. 1.4571 |
| Valve cone | Dezincing free brass CuZn36Pb2As |
| Control diaphragm | EPDM |
| EU RoHS compliance | Out of scope |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| Net weight | 5.608 Kilogram |
| Gross weight | 5.608 Kilogram |
| Packed volume | 27.273 Liter |
| EAN | 5702421543290 |
| HS code | 8481.80 |
| Material | Valve body red bronze CuSn5ZnPb (Rg5); valve seat stainless steel 1.4571; valve cone dezincing free brass CuZn36Pb2As; control diaphragm EPDM |
| Pressure rating | PN 25 (max. differential pressure 12 bar) |
| Temperature range | 2 – 150 °C (medium) |
| Thread standard | ISO 228/1 |
| MOQ | 1 |
Danfoss AVPQT for DN 20 district-heating substations requiring differential-pressure control, flow limitation and return-temperature limitation in one valve, PN 25, return-pipe mounting. Size by the design flow (range 0.16 – 3.5 m³/h, kVS 6.3 m³/h) and set the differential-pressure setpoint within 0.2 – 1 bar; the return-temperature limit is set on the thermostatic element. Confirm the connection (external thread G 1 A (ISO 228/1)) and pressure class (PN 25) against the pipework. Order the thermostatic sensor/element and impulse tube per the AVPQT installation guide. Maximum differential pressure 12 bar, medium temperature up to 150 °C.