Danfoss AVPB differential pressure controller & flow limiter, PN 25, DN 25, 0.2–1 bar adjustable, 0.2–4.5 m³/h, external thread G 1¼ A (003H6448)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6448  ·  HS 8481.80
Danfoss AVPB differential pressure controller & flow limiter, PN 25, DN 25, 0.2–1 bar adjustable, 0.2–4.5 m³/h, external thread G 1¼ A (003H6448)

Danfoss AVPB (003H6448) — self-acting differential pressure control and flow limiter, PN 25, DN 25, for district heating and cooling systems. The AVPB closes on rising differential pressure or when the set maximum flow is exceeded, holding a stable differential pressure across the controlled circuit so connected control valves keep their authority. It combines a control valve, an adjustable flow restrictor and an actuator with one control diaphragm and handle for differential-pressure setting. Differential-pressure setting 0.2–1 bar adjustable; flow rate 0.2–4.5 m³/h; Kvs 8 m³/h. Maximum differential-pressure range 20 bar, media temperature 2–150 °C, cavitation factor z ≥ 0.6, seat leakage 0.02 % Kvs (IEC 60534). Valve body Red bronze CuSn5ZnPb (Rg5); valve cone dezincing-free brass CuZn36Pb2As; seat stainless steel 1.4571; control diaphragm and DP sealing EPDM. Connection External thread G 1¼ A (ISO 228/1), via tailpieces. Media: district heating/cooling circulation water. OEM P/N 003H6448. Technical data quoted verbatim from store.danfoss.com (code 003H6448) and the Danfoss AVPB/AVPB-F (PN 16, 25) operating guide. differential-pressure range 20 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H6448
TypeAVPB
Product groupPressure and flow controllers (differential pressure control & flow limiter)
FunctionSelf-acting differential pressure control and flow limiter with an adjustable differential-pressure setting
Valve sizeDN 25
Pressure classPN 25
ConnectionExternal thread G 1¼ A (ISO 228/1), via tailpieces
Kvs value8 m³/h
Flow rate [m³/h]0.2 - 4.5
Differential pressure setting0.2 - 1 bar (adjustable, factory range)
Max. differential pressure range20 bar
Media temperature2 - 150 °C
Cavitation factor z≥ 0.6
Seat leakage rate0.02 % Kvs (IEC 60534)
Mounting versionReturn
Permissible mediaDistrict heating/cooling circulation water
Valve body materialRed bronze CuSn5ZnPb (Rg5)
Valve cone materialDezincing-free brass CuZn36Pb2As
Valve seat materialStainless steel, mat. no. 1.4571
Diaphragm / DP sealingEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
China RoHSOut of scope
Net weight3.707 kg
Gross weight3.707 kg
EAN5702421539675

Properties

MaterialValve body Red bronze CuSn5ZnPb (Rg5); valve cone dezincing-free brass CuZn36Pb2As; valve seat stainless steel 1.4571; control diaphragm and DP sealing EPDM
Pressure ratingPN 25 (max. differential-pressure range 20 bar)
Temperature range2 to 150 °C (district heating/cooling water)
MOQ1

Compatibility

Danfoss AVPB for DN 25 district-heating/cooling circuits at PN 25. Size by the branch design flow (0.2–4.5 m³/h here) and set the differential-pressure setpoint within 0.2–1 bar. Confirm the connection (External thread G 1¼ A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut set and impulse tube separately. Maximum differential-pressure range 20 bar, media temperature up to 150 °C.