Danfoss AVPA (003H6600) — self-acting differential pressure relief controller, PN 25, DN 40, for district heating and cooling systems. The AVPA is a self-acting differential pressure relief controller; it is normally closed and opens on rising differential pressure, relieving (limiting) the differential pressure across the controlled circuit. It has a control valve, an actuator with one control diaphragm and a spring for the differential-pressure setting. Differential-pressure setting 0.2–1 bar adjustable; Kvs 16 m³/h. Maximum differential-pressure range 16 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.05 % Kvs (IEC 60534). Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm and DP sealing EPDM. Connection External thread G 2 A (ISO 228/1), via tailpieces. Mounting version Bypass. Permissible media: District heating/cooling circulation water (glycolic water up to 30%). OEM P/N 003H6600. Technical data quoted verbatim from store.danfoss.com (code 003H6600). 1.4571; control diaphragm and DP sealing EPDM; Pressure rating: PN 25 (max. differential-pressure range 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Code number | 003H6600 |
| Type | AVPA |
| Product group | Pressure and flow controllers (differential pressure relief controller) |
| Function | Self-acting differential pressure relief controller (opens on rising differential pressure) |
| Valve size | DN 40 |
| Pressure class | PN 25 |
| Connection | External thread G 2 A (ISO 228/1), via tailpieces |
| Kvs value | 16 m³/h |
| Differential-pressure setting | 0.2 - 1 bar (adjustable, factory range) |
| Max. differential pressure range | 16 bar |
| Media temperature | 2 - 150 °C |
| Cavitation factor z | ≥ 0.6 |
| Seat leakage rate | 0.05 % Kvs (IEC 60534) |
| Mounting version | Bypass |
| Permissible media | District heating/cooling circulation water (Glycolic water up to 30%) |
| Valve body material | Ductile iron EN-GJS-400-18-LT (GGG 40.3) |
| Valve cone material | Dezincing free brass CuZn36Pb2As |
| Valve seat material | Stainless steel, mat. No. 1.4571 |
| Diaphragm / DP sealing | EPDM |
| EU RoHS compliance | Out of scope |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| China RoHS | Out of scope |
| Net weight | 6.139 kg |
| Gross weight | 6.359 kg |
| EAN | 5702421541197 |
| Material | Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm and DP sealing EPDM |
| Pressure rating | PN 25 (max. differential-pressure range 16 bar) |
| Temperature range | 2 to 150 °C (district heating/cooling water) |
| MOQ | 1 |
Danfoss AVPA for DN 40 district-heating/cooling circuits at PN 25. Set the differential-pressure setpoint within 0.2–1 bar. Confirm the connection (External thread G 2 A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut set and impulse tube separately. Maximum differential-pressure range 16 bar, media temperature up to 150 °C.