Danfoss AVP differential pressure controller, PN 25, DN 25, kVS 8 m³/h, Δp 0.3 – 2 bar adjustable, flange (003H6377)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6377  ·  HS 8481.80
Danfoss AVP differential pressure controller, PN 25, DN 25, kVS 8 m³/h, Δp 0.3 – 2 bar adjustable, flange (003H6377)

Danfoss AVP (003H6377) — self-acting differential pressure controller, PN 25, DN 25, for district heating and central heating systems. The AVP closes on rising differential pressure, holding a stable differential pressure across the controlled circuit so that connected control valves keep their authority. It consists of a control valve and an actuator with one control diaphragm and a handle for differential-pressure setting. Unlike the AVPB, the AVP is a differential-pressure controller only (no integrated flow limiter). kVS 8 m³/h; differential-pressure setting range 0.3 – 2 bar, adjustable via handle. Maximum differential pressure 20 bar; medium temperature 2–150 °C; leakage 0.02% of kVS (IEC 534). Valve body ductile iron EN-GJS-400-18-LT (GGG 40.3), valve seat stainless steel 1.4571, valve cone dezincing free brass CuZn36Pb2As, control diaphragm EPDM. Connection flange PN 25. Media: circulation water / glycolic water up to 30% (pH 7–10). OEM P/N 003H6377, EAN 5702421538845. Technical data quoted verbatim from the Danfoss AVP PN 25 (VD.55.W6.02) data sheet and store.danfoss.com (code 003H6377). differential pressure 20 bar); Temperature range: 2 – 150 °C (medium); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H6377
TypeAVP
Product groupPressure and flow controllers
DescriptionSelf-acting differential pressure controller (district heating), adjustable setting, flow mounting
Valve sizeDN 25
Pressure classPN 25
kVS value8 m³/h
Connectionflange, PN 25
Differential pressure setting0.3 – 2 bar (adjustable)
Max. differential pressure20 bar
MediumCirculation water / glycolic water up to 30% (pH 7–10)
Medium temperature2 – 150 °C
Leakage (IEC 534)0.02% of kVS
Mounting versionFlow
Stem positionNormally open
Valve bodyDuctile iron EN-GJS-400-18-LT (GGG 40.3)
Valve seatStainless steel, mat. No. 1.4571
Valve coneDezincing free brass CuZn36Pb2As
Control diaphragm / sealingEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
Net weight7.774 Kilogram
Gross weight7.774 Kilogram
Packed volume11.454 Liter
EAN5702421538845
HS code8481.80

Properties

MaterialValve body ductile iron EN-GJS-400-18-LT (GGG 40.3); valve seat stainless steel 1.4571; valve cone dezincing free brass CuZn36Pb2As; control diaphragm EPDM
Pressure ratingPN 25 (max. differential pressure 20 bar)
Temperature range2 – 150 °C (medium)
MOQ1

Compatibility

Danfoss AVP for DN 25 district-heating or central-heating circuits, PN 25. Size by the branch design flow (kVS 8 m³/h) and set the differential-pressure setpoint within 0.3 – 2 bar. Confirm the connection (flange, PN 25) and pressure class (PN 25) match the pipework. For combined differential-pressure control and flow limiting use the AVPB/AVPQ instead. Maximum differential pressure 20 bar, medium temperature up to 150 °C.