cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss AVP differential pressure controller, PN 25, DN 20, kVS 6.3 m³/h, Δp 0.2 – 1 bar adjustable, external thread G 1 A, return mounting (003H6286)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6286  ·  HS 8481.80
Danfoss AVP differential pressure controller, PN 25, DN 20, kVS 6.3 m³/h, Δp 0.2 – 1 bar adjustable, external thread G 1 A, return mounting (003H6286)

Danfoss AVP (003H6286) — self-acting differential pressure controller, PN 25, DN 20, for mounting in the return pipe, for district heating and central heating systems. The AVP closes on rising differential pressure, holding a stable differential pressure across the controlled circuit so that connected control valves keep their authority. It consists of a control valve and an actuator with one control diaphragm and a handle for differential-pressure setting. Unlike the AVPB, the AVP is a differential-pressure controller only (no integrated flow limiter). kVS 6.3 m³/h; differential-pressure setting range 0.2 – 1 bar, adjustable via handle. Maximum differential pressure 20 bar; medium temperature 2–150 °C; leakage 0.02% of kVS (IEC 534). Valve body red bronze CuSn5ZnPb (Rg5), valve seat stainless steel 1.4571, valve cone dezincing free brass CuZn36Pb2As, control diaphragm EPDM. Connection external thread G 1 A (ISO 228/1), via tailpieces (ordered separately). Media: circulation water / glycolic water up to 30% (pH 7–10). OEM P/N 003H6286, EAN 5702421538050. Technical data quoted verbatim from the Danfoss AVP PN 25 (VD.55.W6.02) data sheet and store.danfoss.com (code 003H6286). differential pressure 20 bar); Temperature range: 2 – 150 °C (medium); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H6286
TypeAVP
Product groupPressure and flow controllers
DescriptionSelf-acting differential pressure controller (district heating), adjustable setting, return mounting
Valve sizeDN 20
Pressure classPN 25
kVS value6.3 m³/h
Connectionexternal thread G 1 A (ISO 228/1)
Differential pressure setting0.2 – 1 bar (adjustable)
Max. differential pressure20 bar
MediumCirculation water / glycolic water up to 30% (pH 7–10)
Medium temperature2 – 150 °C
Leakage (IEC 534)0.02% of kVS
Mounting versionReturn
Stem positionNormally open
Valve bodyRed bronze CuSn5ZnPb (Rg5)
Valve seatStainless steel, mat. No. 1.4571
Valve coneDezincing free brass CuZn36Pb2As
Control diaphragm / sealingEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
Net weight3.402 Kilogram
Gross weight3.402 Kilogram
Packed volume9.562 Liter
EAN5702421538050
HS code8481.80

Properties

MaterialValve body red bronze CuSn5ZnPb (Rg5); valve seat stainless steel 1.4571; valve cone dezincing free brass CuZn36Pb2As; control diaphragm EPDM
Pressure ratingPN 25 (max. differential pressure 20 bar)
Temperature range2 – 150 °C (medium)
Thread standardISO 228/1
MOQ1

Compatibility

Danfoss AVP for DN 20 district-heating or central-heating circuits, PN 25, return-pipe mounting. Size by the branch design flow (kVS 6.3 m³/h) and set the differential-pressure setpoint within 0.2 – 1 bar. Confirm the connection (external thread G 1 A (ISO 228/1)) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut set and impulse tube separately. The flow-mounting counterpart carries a different code — verify the mounting version against the installation drawing. For combined differential-pressure control and flow limiting use the AVPB/AVPQ instead. Maximum differential pressure 20 bar, medium temperature up to 150 °C.

Attached Documents