Danfoss AVP-F (003H6368) — self-acting differential pressure controller, PN 25, DN 50, for district heating and central heating systems. The AVP-F is the fixed-setpoint version of the AVP: the differential pressure is factory-preset and sealed (no adjustment handle), holding a constant differential pressure across the controlled circuit so that connected control valves keep their authority. Unlike the AVPB, the AVP-F is a differential-pressure controller only (no integrated flow limiter). kVS 25 m³/h; fixed differential-pressure setting 0.5 bar (factory-preset, sealed). Maximum differential pressure 16 bar; medium temperature 2–150 °C; leakage 0.05% of kVS (IEC 534). Valve body ductile iron EN-GJS-400-18-LT (GGG 40.3), valve seat stainless steel 1.4571, valve cone dezincing free brass CuZn36Pb2As, control diaphragm EPDM. Connection flange PN 25. Media: circulation water / glycolic water up to 30% (pH 7–10). OEM P/N 003H6368, EAN 5702421539057. Technical data quoted verbatim from the Danfoss AVP PN 25 (VD.55.W6.02) data sheet and store.danfoss.com (code 003H6368). differential pressure 16 bar); Temperature range: 2 – 150 °C (medium); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Code number | 003H6368 |
| Type | AVP-F |
| Product group | Pressure and flow controllers |
| Description | Self-acting differential pressure controller (district heating), fixed setting, return mounting |
| Valve size | DN 50 |
| Pressure class | PN 25 |
| kVS value | 25 m³/h |
| Connection | flange, PN 25 |
| Differential pressure setting | 0.5 bar (fixed) |
| Max. differential pressure | 16 bar |
| Medium | Circulation water / glycolic water up to 30% (pH 7–10) |
| Medium temperature | 2 – 150 °C |
| Leakage (IEC 534) | 0.05% of kVS |
| Mounting version | Return |
| Stem position | Normally open |
| Valve body | Ductile iron EN-GJS-400-18-LT (GGG 40.3) |
| Valve seat | Stainless steel, mat. No. 1.4571 |
| Valve cone | Dezincing free brass CuZn36Pb2As |
| Control diaphragm / sealing | EPDM |
| EU RoHS compliance | Out of scope |
| Net weight | 13.598 Kilogram |
| Gross weight | 13.598 Kilogram |
| Packed volume | 25.662 Liter |
| EAN | 5702421539057 |
| HS code | 8481.80 |
| Material | Valve body ductile iron EN-GJS-400-18-LT (GGG 40.3); valve seat stainless steel 1.4571; valve cone dezincing free brass CuZn36Pb2As; control diaphragm EPDM |
| Pressure rating | PN 25 (max. differential pressure 16 bar) |
| Temperature range | 2 – 150 °C (medium) |
| MOQ | 1 |
Danfoss AVP-F for DN 50 district-heating or central-heating circuits, PN 25. Size by the branch design flow (kVS 25 m³/h) and confirm the fixed differential-pressure setting (0.5 bar). Confirm the connection (flange, PN 25) and pressure class (PN 25) match the pipework. For combined differential-pressure control and flow limiting use the AVPB/AVPQ instead. Maximum differential pressure 16 bar, medium temperature up to 150 °C.