Danfoss AVP-F differential pressure controller, PN 25, DN 50, kVS 25 m³/h, Δp 0.2 bar fixed, flange (003H6362)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6362  ·  HS 8481.80
Danfoss AVP-F differential pressure controller, PN 25, DN 50, kVS 25 m³/h, Δp 0.2 bar fixed, flange (003H6362)

Danfoss AVP-F (003H6362) — self-acting differential pressure controller, PN 25, DN 50, for district heating and central heating systems. The AVP-F is the fixed-setpoint version of the AVP: the differential pressure is factory-preset and sealed (no adjustment handle), holding a constant differential pressure across the controlled circuit so that connected control valves keep their authority. Unlike the AVPB, the AVP-F is a differential-pressure controller only (no integrated flow limiter). kVS 25 m³/h; fixed differential-pressure setting 0.2 bar (factory-preset, sealed). Maximum differential pressure 16 bar; medium temperature 2–150 °C; leakage 0.05% of kVS (IEC 534). Valve body ductile iron EN-GJS-400-18-LT (GGG 40.3), valve seat stainless steel 1.4571, valve cone dezincing free brass CuZn36Pb2As, control diaphragm EPDM. Connection flange PN 25. Media: circulation water / glycolic water up to 30% (pH 7–10). OEM P/N 003H6362, EAN 5702421538937. Technical data quoted verbatim from the Danfoss AVP PN 25 (VD.55.W6.02) data sheet and store.danfoss.com (code 003H6362). differential pressure 16 bar); Temperature range: 2 – 150 °C (medium); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H6362
TypeAVP-F
Product groupPressure and flow controllers
DescriptionSelf-acting differential pressure controller (district heating), fixed setting, return mounting
Valve sizeDN 50
Pressure classPN 25
kVS value25 m³/h
Connectionflange, PN 25
Differential pressure setting0.2 bar (fixed)
Max. differential pressure16 bar
MediumCirculation water / glycolic water up to 30% (pH 7–10)
Medium temperature2 – 150 °C
Leakage (IEC 534)0.05% of kVS
Mounting versionReturn
Stem positionNormally open
Valve bodyDuctile iron EN-GJS-400-18-LT (GGG 40.3)
Valve seatStainless steel, mat. No. 1.4571
Valve coneDezincing free brass CuZn36Pb2As
Control diaphragm / sealingEPDM
EU RoHS complianceOut of scope
Net weight13.404 Kilogram
Gross weight13.404 Kilogram
Packed volume14.553 Liter
EAN5702421538937
HS code8481.80

Properties

MaterialValve body ductile iron EN-GJS-400-18-LT (GGG 40.3); valve seat stainless steel 1.4571; valve cone dezincing free brass CuZn36Pb2As; control diaphragm EPDM
Pressure ratingPN 25 (max. differential pressure 16 bar)
Temperature range2 – 150 °C (medium)
MOQ1

Compatibility

Danfoss AVP-F for DN 50 district-heating or central-heating circuits, PN 25. Size by the branch design flow (kVS 25 m³/h) and confirm the fixed differential-pressure setting (0.2 bar). Confirm the connection (flange, PN 25) and pressure class (PN 25) match the pipework. For combined differential-pressure control and flow limiting use the AVPB/AVPQ instead. Maximum differential pressure 16 bar, medium temperature up to 150 °C.

Attached Documents