Danfoss AVP (003H6211) — self-acting differential pressure controller, PN 16, DN 32, for district heating and central heating systems. The AVP closes on rising differential pressure, holding a stable differential pressure across the controlled circuit so that connected control valves keep their authority. Unlike the AVPB, the AVP is a differential-pressure controller only (no integrated flow limiter). It consists of a control valve and an actuator with one control diaphragm and a handle for differential-pressure setting. kVS 10 m³/h; differential-pressure setting range 0.2 – 1.0 bar, adjustable. Maximum differential pressure 12 bar; medium temperature 2–150 °C; leakage 0.05% of kVS (IEC 534). Valve body red bronze CuSn5ZnPb (Rg 5), valve seat stainless steel 1.4571, valve cone dezincing-free brass CuZn36Pb2As, control diaphragm EPDM. Connection external thread G 1 ¾ A (ISO 228/1) via tailpieces (ordered separately). Media: circulation water / glycolic water up to 30% (pH 7–10). OEM P/N 003H6211. Technical data quoted verbatim from the Danfoss AVP / AVP-F (PN 16) data sheet and store.danfoss.com (code 003H6211). differential pressure 12 bar); Temperature range: 2 – 150 °C (medium); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Code number | 003H6211 |
| Type | AVP |
| Product group | Pressure and flow controllers |
| Description | Self-acting differential pressure controller (district heating), adjustable setting, return/flow mounting |
| Valve size | DN 32 |
| Pressure class | PN 16 |
| kVS value | 10 m³/h |
| Connection | External thread G 1 ¾ A (ISO 228/1), via tailpieces |
| Differential pressure setting range | 0.2 – 1.0 bar (adjustable) |
| Max. differential pressure | 12 bar |
| Medium | Circulation water / glycolic water up to 30% (pH min. 7, max. 10) |
| Medium temperature | 2 – 150 °C |
| Leakage (IEC 534) | 0.05% of kVS |
| Mounting version | Return (AVP also flow-mountable) |
| Valve body | Red bronze CuSn5ZnPb (Rg 5) |
| Valve seat | Stainless steel, mat. No. 1.4571 |
| Valve cone | Dezincing-free brass CuZn36Pb2As |
| Control diaphragm / sealing | EPDM |
| EU RoHS compliance | Yes with exemptions (6(c)) |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| Net weight | 2.53 kg |
| Gross weight | 2.534 kg |
| EAN | 5702421537350 |
| HS code | 8481.80 |
| Material | Valve body red bronze CuSn5ZnPb (Rg 5); valve seat stainless steel 1.4571; valve cone dezincing-free brass CuZn36Pb2As; control diaphragm EPDM |
| Pressure rating | PN 16 (max. differential pressure 12 bar) |
| Temperature range | 2 – 150 °C (medium) |
| MOQ | 1 |
Danfoss AVP for DN 32 district-heating or central-heating circuits. Size by the branch design flow (kVS 10 m³/h) and set the differential-pressure setpoint within 0.2 – 1.0 bar. Confirm the connection (external thread G 1 ¾ A, ISO 228/1) and pressure class (PN 16) match the pipework; order the matching tailpiece/union-nut set and impulse tube separately. For combined differential-pressure control and flow limiting use the AVPB instead. Maximum differential pressure 12 bar, medium temperature up to 150 °C.